City of Oshkosh
Division of Inspection Services
215 Chu",h Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wius
ON THE WATER
February 20, 2006
Paul Sobieck
Milwaukee Stove & Furnace
2442 Hutson Road
Green Bay, WI 54303
KDC Properties
PO Box 166
Oshkosh, WI 54903
Site:
12i2NMainSt.
Oshkosh WI 5490i
For:
Description: HV AC system for Tenant space alterations
Object Type: HV AC only
Class of Construction: VB - 864 Sq Ft.; UnsprinkIered
Occupancy: B: Business I Office
Plan Number: RS-12-0206
!
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as derIDed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Hem(s) I Conditions:
IMC 304.1 Equipment and appliances shall be installed as required by the terms of their approval, in
accordance with the conditions of the listing, the manufacture's instructions and this code.
304.8 Clearances ftom grade. Equipment and appliances installed at grade level shall be supported on a
level concrete slab or other approved material extending above adjoining grade or shall be suspended a
minimum of 6 inches (152 mm) above adjoining grade.
IMC 401.5 Opening Location Outside air exhaust and intake openings shall be located a minimum of 10
feet (3048 mm) ftom lot lines or buildings on the same lot. Where openings ftont on a street or public way,
the distance shall be measured to the centerline of the street or public way. Property lines are not shown
on plans, however based on records on jüe it would appear that the North side of the building is at or
near the property line, leaving less than lOfeet between the building and property line.
IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
ftom any hazardous or noxious contaminant such as vents, chimneys, plumbing vents, streets, alleys,
parking lots and loading docks.
Comm 65.0304 (4) Additional combustion air intake requirement. Mounting height of the combustion
air intakes shall have the lowest side of outside air intake openings located at least 12 inches (305 mm)
vertically ftom the adjoining grade level.
..\OSfIKOSHMISFS\1.'SERS'.briwm\2006 Comm Pl"n Review\P5-l2-iJ20612l2 N \Üìn $1. TNACÚnly.d()c
Page I of2