HomeMy WebLinkAbout0009775
~
OSHKOSH
ON THE WATER
Issue Date 12115104 - Compliance Date 1114105
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance No
Address
318 N MAIN ST
Sent to
~ Owner
Name
I EXCLUSIVE COMPANY CORP
Address
416 N MAIN ST
City
OSHKOSH
State Zip Code
WI 54901 -4978
---
Introduction
U Required for Occupancy I Occupancy Commercial
n inspection on 12-14.04 revealed the following items to correct. These must be corrected and reinspected prior to
ccupancy.
Item # Code COMM 1003.2.8 Compliance Not Checked Compliance Date 0111412005
Description his is an advisory note: The track curtains shall not be placed so as to obstruct the exit passageways (wood grain floor
isles.) If these curtains are found to obstruct these aisles in future inspections. the owner will be required to modify the
12115104 rackso it does not continue over the exit access aisles.
Last
Updated
Item # Code COMM 62.0906 Compliance No Compliance Date 0111412005
Description Fire extinguishers shall be provided on each floor. All areas to be within 75 lin It of a fire extinguisher.
IMMEDIATELY
12115104
Last
Updated
wivl~e~ ~~
~þ-
Item #
Description
12115104
Last
Updated
Code COMM 1003.2.10 Compliance No Compliance Date 0111412005 IMMEDIATELY
~' ~' - .00 W ,~. """" OOM, " 'œ"" - - W ,- ~, """" """
9775
Page 1 of2
~
OSHKOSH
ON THE WATER
IssueDate 12/15104 -
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 1114105
Compliance No
Address
318 N MAIN ST
Sent to
~ Owner
Name
I EXCLUSIVE COMPANY CORP
Address
416 N MAIN ST
City
OSHKOSH
State Zip Code
WI 54901 -4978
---
Introduction
U Required for Occupancy I Occupancy Commercial
n inspection on 12-14-04 revealed the following items to correct. These must be corrected and reinspected prior to
ccupancy.
Item #
4
Code COMM 54 Compliance No Compliance Date 0111412005 IMMEDIATELY
Provide smok~capable of shutting dOwn;!;! ::JJ.-sy~tem in all systems serving more than one room.
S.v .Ç~o* M7
Description
12115104
Last
Updated
Summarv
Jccupancy is prohibited until approvals are obtained from all inspectors involved (Building, HVAC, Electric, Plumbing, Fire
Dept.)
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and. return it to the Inspection Services Division by the Compliance Date of 1114105
Office hours for obtaining permits are Monday through Friday 7:30-8:30 a.m. and 12:30-1 :30 p.m. or by appointment. To schedule
inspections pie se call the Inspection Request line at 236-5128 noting the address, permit number (when applicable), and the
nature of w 0 be i spected.
,.#
Signature
Print Name
Company
Signature
Date
Also Sent to:
~ Bldg
U Elec
~ HVAC
U Plbg
U Designer
U Other
~ Inspector
---
I CR MEYER
I
I GARTMAN MECHANICAL SERVICES
I
I
I
I Fire Department
895 W 20TH AVE
OSHKOSH
WI 54902 -0
---
PO BOX 2264
OSHKOSH
WI 54903 -2264
---
---
---
-0000
---
9775
Page2of2
EIVED
¿,
GMS, Inc.
Gartman Mechanical Services
Heating. Ventilating. Air conditioning. Sheet Metal
P.O. Box 2264 520 West Southpark Avenue
Oshkosh, WI 54903
(920) 231-5530 Fax (920) 231-0486
JAN 2 1 2005
DEPARTMENT OF
COMMUNITY DEVElOPMENT
January 12, 2004
City of Oshkosh
Inspection Department
215 Church Avenue
P.O. Box 1130
Oshkosh, WI 54903-1130
Attn: Allyn Dannhoff
RE: Exclusive Company-Smoke Detection
Dear Allyn,
Following a correction notice of 12-15-04, we have had some discussions with Mr. G, the
owner of the Exclusive Company concerning a requirement for smoke detection, unit
shut down, and annunciation of alarm condition. This is for the first level or main level
of his new store on Main Street, Oshkosh, WI.
We had the discussion about the detection being required only because of a one single
approximate 4' x 10 or 12' room at the east side of the building which is separated from
the single large main area.
We have a letter from the owner indicating that he intends not to use this as an office
because of this situation. We had quoted the detection, and annunciation and he opted
not to cover this cost even though he realized that it was a legitimate change.
Weare pulling the diffuser from this area, and capping the take off on the duct main.
This should resolve the need and request for smoke detection on this particular unit. Be
advised that this work will have been done on 1-12-05.
We enclose a copy of the letter from the Exclusive Company advising us on taking this
method of resolving this situation.
If you have questions, please contact us.
Very T rul Y~o .ç' fl~
c9d '"' - ,t7~
Keit~auI, .~
KNP/jk
Enclosure
J~
+
lJ1)e
416 North Main Street
Oshkosh, Wisconsin 54901
December 22, 2004
Keith Paul
Gartman Mechanical Services
520 W. Southpark Avenue
P.O. Box 2264
Oshkosh, WI 54903-2264
Dear Keith,
After considering the additional cost of $1 080.00 to install a smoke detector in the
area we intended to use as a small office, we have decided to use the area for
storage instead. We do not feel that it would be in our best interest to spend the
additional money as the room was only going to be used on a minimal basis.