HomeMy WebLinkAbout0118358-HVAC
e
OSHKOSH
ON THE WATER
Job Address 320 E FERNAU AVE
CITY OF OSHKOSH
No
118358
HVAC PERMIT - APPLICATION AND RECORD
Owner
M BRICKHAM HOLDINGS LLC
Create Date 02124/2006
Plan R1-109-1105
1 1 Oil
Category 512 - Ind. & Comm-Both
1"1 Electric
I 1 Solar
I I Solid
Contractor MCM AIR INC
Fuel 1"1 Gas
System 0 New
~ Forced Air
I 1 Electric
Chimney Type Chimney A
Heat Loss K ) As Approved
BTU Rate K ) As Per Plan
U Radiant
I I HotWater
n Replace
U Steam
I I Suppl.
n Other
U Vent
Chimney B
( ) Existing
Direct Vent
~NC I
I 1 Con. Burner I
Not Applicable
Use/Nature Install FA HVAC system for offices on mezzanine. - Equipment required to be screend per plan on file.
ofWork
( ) Variable
. Not Applicable
. Other
Value
Value
Fees: Valuation
$11,000.00
Plan Approval
$0.00
Permit Fee Paid
$165.00
Issued By:
Date 03/0212006
D Permit vo~
Parcelld # 1519603100
In the performance of this work, I a9ree to perform all work pursuant to rules govemin9 the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
AgenVOwner
Address
6122 COUNTY ROAD M
WINNECONNE
WI 54986 - 9780 Telephone Number
920-582-4402
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
~
OIHKOfH
ON THE WATER
City of Oshkosh
Division ofInspection Services
215 Church Avenue
PO Box mo
Oshkosh WI 54903-1130
www.cLoshkosh.wLus
December 5, 2005
Mark Christens
Temperature Systems Inc.
2200 S Ashland Ave
Green Bay, WI 54304
M Brickham Holdings LLC
320 E Fernau Ave
Oshkosh, WI 54901
Site:
Brickham Machine Co
320 E Fernau Ave
Oshkosh WI 54901
For:
Description: Tenant space alterations
Object Type: HV AC only
Class of Construction: TIm - 2400 Sq Ft.;
Occupancy: B: Business Office
Plan Number: R1-109-1105-H
Uusprinklered
The submittal described aboye has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as deemed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
mc 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
from any hazardous or noxious contaminant such as vents, chimneys, plumbing vents, streets, alleys,
parking lots and loading docks.
401.5.2 Exhaust openings. Outside exhaust openings shall be located so as not to create a nuisance.
Exhaust air shall not be directed onto walkways.
MUN 30-35 (1)(5) All rooftop and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally mc 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7. Provide detail showing AlC location and screening. No HV AC permit
will be issued until screening plans have been provided and approved.
Page 1 of2
SUBMIT:
IECC 503.3.3.7 [Comm 63.0503(2)(1)] Balancing and documentation ofthe HV AC system shall conform
to the !MC. Balancing report required to be submitted prior to final occupancy being allowed.
Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Respe~¿
~
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.Mto 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
230.00
230.00
0.00
(\)<1'01 Pian
,\".
Only.doc
Page20f2
HVAC Permit Work Card
Job Address 320 E FERNAU AVE
Permit Number
118358 Create Date 02/24/2006
Owner
M BRICKHAM HOLDINGS LLC
Contractor MCM AIR INC
Category 512 -Ind. & Comm-Both
Plan R1-109-1105
Fuel ~ IT2C:J ~ Electric I ~ ~ Value $11,000.00
System PI New n Replace 1 D Other I
~ Forced Air I []Radiant I U Steam I ~C I U Vent I
U Electric I U Hot Water I U Suppl. I llion. Burner I
Chimney Type ,0 Chimney A 0 Chimney B 0 DirectVent . Not Applicable
Heat Loss P As Approved 0 Existing . Not Applicable I Value
BTU Rate 0 As Per Plan 0 Variable . Other I Value
Use/Nature Install FA HVAC system for offices on mezzanine. - Equipment required to be screend per plan on file.
of Work
Inspections:
Date 1/25/2006
Type
Inspector Allyn Dannhoff
approved
NO CONCERNS NOTED-CLOSE FILE WHEN HVAC PERMIT IS ISSUED / HVAC PERMIT ISSUED 3/2/06
DatelTime requested:
Notice Type:
Phone Number:
Access:
Ready DatelTime:
Requested By:
0 Reinspect Fee 0 Fee Waived
D Reinspect Fee Paid