Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
2002-Electric
OSHKOSH OPERA Fax :9202365933 Jan 10 2003 16:36 P.O2 THREE PHASE SHORT CIRCUIT CALCULATION 1/1012003 ~'~.F' Address: 453 Washburn Service Size: 800 am Description: . 'qŠJ~I~:¡i¡fð @+~~!#ie~ 3 symmetrical Short Circuit Curren! for a Bolted Fault: Design sce for a 500 KVA Padmount Tr:ansformer: 19,542 31,457 Amps Amps CALCULATIONS FOR BOLTED FAULT SEC. SIDE IMPEDANCES Location R(OhmS) X IOhms\ Sub Exit 0.00000 0.00119 Cust. Primary 0.00000 0.00000 Tr¡¡nsformer 0.00077 0.01229 Secondary 0.00000 0,00000 Service 0.00064 0,00064 Total 0.00141 0.01411 Totallmped, 12) 0.014180903 Symmelrlcal Short Circuit 19,542 Current for a Boned Fault: Amos Electric Permit Work Card Job Address 425 N WASHBURN ST Permit Number 98520 Create Date 11/08/2002 Owner SHORELAND DEVELOPMENT CORPORAT!- Category 642.- Comm'~rcial-New Building Wiring Contractor SCHOMMER ELECTRiCAL CONTRACTJr Service p New 0 ChangeO Temp ON/A I Type 0 Overhead Volts 120/208 Circuits 0 Amps ~ Switches 0 . Underground ON/A Fixtures Receptacles Value $23,700.00 Fee $222.00 0 Appliances Use/Nature ofWork NEW Used Car Dealership/ Wire new used cars store, 'THIS PERMIT DOES NOT INCLUDE OWNER PURCHASES - A SEPARATE PERMIT IS REQUIRED. Inspections: Date 11/11/2002 Type Rough In Inspector Kevin Benner approved w/cond, E.C, never called for an inspection. I had a phone conversation Earl VanEperen on 11/8/02 @ 9:37 AM about another project when I asked him about the U,G. for this project. Will be approved with a minimum of 22" of gravel & biacktop. There is 52" from theclay to the top of the light pole base. All conduits were buried when I inspected. DatelTime requested: 11/0812002 09:37 AM Access: Notice Type: Phone Number: Ready DatelTime: 11/11/2002 01 :40 PM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid - - - -- - - - - - - - - - -- - - - - - - - - - - - - - - -- - - - - - - - - - - --- --- - - - -- - -- - - - - - - - - - - - - - - --- - -- - - - - - - -. Date 02/19/2003 Type Consultation Inspector Kevin Benner approved Discuss XFMR location. Discussed keeping XFMR out of dedicated space. Date/Time requested: 02119/2003 07:44 AM Access: Meet Lee on site Notice Type: Phone Number: Ready DatelTime: 02119/200300:00 AM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid -----------------------------------------------------------------------------------. Electric Permit Work Card Job Address 425 N WASHBURN ST Owner SHORELAND DEVELOPMENT CORPORAn Permit Number ~ Create Date 11/08/2002 Contractor SCHOMMER ELECTRICAL CONTRACTJr Category 642 - Commerciai-New Building Wiring Service pNew 0 ChangeO Temp ON/A I Type 0 Overhead . Underground 0 N/A Volts 120/208 Circuits 0 Fixtures 0 Amps 800 Switches - Receptacles 0 Fee $222.00 0 Value $23,700,00 Appliances Use/Nature of Work EW Used Car Dealership/ Wire new used cars store. 'THIS PERMIT DOES NOT INCLUDE OWNER PURCHASES - A SEPARATE PERMIT IS REQUIRED. Inspections: Type Service Inspector Kevin Benner not approved Date 02/26/2003 Faxed request No access to the CT cabinet DatelTime requested: 02124/2003 12:21 PM Access: Notice Type: Phone Number: 920-731-2299 Ready DatelTime: 02124/2003 12:21 PM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid SCHOMMER ELECTRICAL CON-Bob - - - - - - - - - - - - - -- - - - --- - - - - - - - - - ---- - - - --- - - - - - - - - - - - - -- ---- -- ----- - - -- - - - - - - - - -- --- -. Date 02127/2003 Type Re Service Inspector Kevin Benner approved I called WPS to have the CT cabinet unlocked. Faxed to WPS 2128/03. mailed 3/3/03 DatelTime requested: 02/27/2003 08:25 AM Access: Notice Type: Phone Number: Ready Date/Time: 02127/2003 08:27 AM Requested by: -- 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid - - - - - --- --- - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -- ---- - - - --- - - ---------- - - - - - - - - ---. Electric Permit Work Card Owner SHORELAND DEVELOPMENT CORPORAn Permit Number 98520 Create Date 11/0812002 Contractor SCHOMMER ELECTRICAL CONTRACTlt Job Address 425 N WASHBURN ST " Category 642.- Commercial-New Building Wiring 120/208 0 ChangeO Temp 0 N/A I Type Q Overhead Circuits 0 . Underground 0 N/A Service p New Volts Fixtures ~ Amps ~ Switches 0 Receptacles 0 Fee $222.00 0 Value $23,700,00 Appliances Use/Nature of Work ~~V;;~~e~u~~~:~I~~~i~ :~~~;~s~~~7/I~r~E;;r~~:OERMiT DOES NOT INCLUDE Inspections: Date 04/29/2003 Type Rough In Inspector Kevin Benner approved w/cond. Area under storage mezzo Have Bidg Insp, check mezz buildup. DatelTime requested: 04/29/2003 08:32 AM Access: Notice Type: Phone Number: Ready DatelTime: 04/29/2003 00:00 PM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid - - - - - - - - - - - - - -- - - - - - - - - - - - - ----- - -------- - -- - - - - - - - - - - - - - - --- - - - - - - --- - - - - - - - - - - - - -. Date 06/1312003 Type Final Inspector Kevin Benner cancelled Partial final (showroom & exterior) Floor was just tiled, no grout, no access Date/Time requested: 06/11/2003 12:29 PM Access: Notice Type: Phone Number: Ready DatelTime: 06/11/200312:29 PM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid --- - - - -------- - - - - -- - - - - - - ------------- - - - - - - - - - - - - - - - - - - - --- - - ---- --- - - - - - - --- - - - -. Electric Permit Work Card Job Address 425 N WASHBURN ST Permit Number 98520 Create Date 11/0812002 Owner SHORELAND DEVELOPMENT CORPORAn Contractor SCHOMMER ELECTRICAL CONTRACTlt - Category 642- Commercial-New Building Wiring Service p New Volts 120/208 0 ChangeO Temp 0 N/A I Type 0 Overhead Circuits 0 . Underground 0 N/A Fixtures 0 - Amps ~ Switches 0 Receptacles 0 Fee $222.00 0 Value $23,700.00 Appliances Use/Nature of Work NEW Used Car Dealership/ Wire new used cars store, 'THIS PERMIT DOES NOT INCLUDE þWNER PURCHASES - A SEPARATE PERMIT IS REQUIRED, Inspections: Date 06/17/2003 Type Re Final Inspector Kevin Benner cancelled I-"~- Date/Time requested: 06/11/2003 12:29 PM Access: Notice Type: Phone Number: Ready DatelTime: 06/11/200312:29 PM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid - - - - - - - --- - - ------ - - - - - - - ---- - - - - - - - - -- ----- - - - - - - - - - - - - - - - - - - - - - - --- -- - - - - - - - - - - --. Date 06/26/2003 Type Re Final Inspector Kevin Benner not approved Electrical Inspector was not able to be at work that day. See field notes, called Bob Schommer to review DatelTime requested: 06/19/2003 09:46 AM Access: Notice Type: Phone Number: Ready DatelTime: 06/23/2003 09:00 AM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid - - - - - - - - - - - ------- - - - - - - - - - - - ---- - - - - - - - - - - - - -- --- - ---- ---- -- - -- -- - - - - - -- -------- - -. Electric Permit Work Card Job Address 425 N WASHBURN ST Permit Number 98520 Create Date 11/08/2002 Owner SHORELAND DEVELOPMENT CORPORATI' Contractor SCHOMMER ELECTRICAL CONTRACTlr Category 64a - Commercial-New Building Wiring Service p New 0 ChangeO Temp ON/A I Type 0 Overhead Volts 120/208 Circuits 0 Amps 800 Switches ~ . Underground 0 N/A Fixtures ~ Receptacles 0 Fee $222.00 0 Value $23,700.00 Appliances Use/Nature of Work NEW Used Car Dealership/ Wire new used cars store. 'THIS PERMIT DOES NOT INCLUDE JWNER PURCHASES - A SEPARATE PERMIT IS REQUIRED. Inspections: Date 07/15/2003 Type Consultation Inspector Kevin Benner 1) installing lights to best guess!? 2) XFMR bonding & grounding. 3) Housekeeping, 4) Carwash eq. nolin, 5) ExfannotW,P. DatelTime requested: 07/14/2003 02:26 PM Access: Meet E.C. (Lee) on site Ready Date/Time: 07/15/200311:00AM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid Notice Type: Phone Number: 731-2299 SCHOMMER ELECTRICAL CON (Bob) - - - --- - - - - - - - - - - - --- - - - - - -- ------- -- - - - - - - - ----- - - - - - - - - - - - - - - - -- - - - - - - - ------- - - - -, Date 07/17/2003 Type Re Final Inspector Kevin Benner approved w/cond, Faxed request - Note: everything on Kevin's list is done. 1) Breaker loks not installed for emergency lights. 2) Carwash not installed, 3) Light pole installation instructions from the owner. DatelTime requested: 07/1712003 08:14 AM Access: Notice Type: Phone Number: 920-731-2299 Ready Date/Time: 07/17/2003 08:14 AM Requested by: 0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid SCHOMMER ELECTRICAL CON-Bob - - - - - - - - - - - - - ----- - - - - - - ------ - - - - - - - - - - - - - ----- - - - - - - - - - - - -- - - - - - - - - - - ---- - ---- - - -.