RE:
FIRE PROTECTION SYSTEM INSTALLATION
OLD NAVY - PRIME OUTLET MALL
3001 SOUTH WASHBURN
OSHKOSH, WISCONSIN 54904
AHERN FIRE PROTECTION WORK ORDER No. 991895
Dear Brian:
Enclosed is a copy of the Contractor's Material and Test Certificates covering the above-referenced
Fire Protection System Installation for your files.
Very truly yours,
AHERN FIRE PROTECTION
AdiV~.'. ..0.fJ.F.Ahernc~.~
¿1m ¡j¿~
JeffR. Batterman
Service Supërintë¡jdent
JRB/ksj
LCITYI2.12.05.000
An Equal Opportunity Employer
AHERN FIRE PROTECTION
Còntractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and wünessed by an owner's representative. All defects shall be
corrected and system left in senrice before contractor's pelSOnnal finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, own""" and contractor, II is understood the
owner's representative's signalure in no way prejudices any claim against contractor for faully malarial, poor workmanship, or failure to comply wüh approving
authoritv'sreauirements or local ontinances.
PROPERTY NAME Old Navy - Prime Outlet Mall AFP W.O.#: 991895 I DATE: November 21, 2005
PROPERTY ADDRESS 3001 South Washburn Oshkosh, WI 54904
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
1. Oshkosh Fire Department (Battalion Chief -- Stu Schrotlky)
2. City of Oshkosh (Building Inspector -- Brian Noe)
3.
4.
ADDRESS
Plans 1. 101 Court Street -- Oshkosh, WI 54901
2. 215 Church Avenue -- PO Box 1130 - Oshkosh, WI 54901
3.
4.
INSTALLATION CONFORMS TO ACCEPTED PLANS Ev~S DNO
EQUIPMENT USED IS APPROVED ' YES DNO
IF NO, EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION .£!YES DNO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
INSTRUCTIONS IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
"""No.'s2&3"'0 1. SYSTEM COMPONENTS INSTRUCTION DYES ~O
be"""""'odbyAFP 2, CARE AND MAINTENANCE INSTRUCTIONS ~ ~ES -~
atdoseouttime.
3. NFPA 25 YES NO
LOCATION OF SUPPLIES BUILDINGS
SYSTEM System #1
MAKE MODEL YEAR OF K- QUANTITY TEMPERATURE
MANUFACTURE FACTOR RATING
Vi~na Micromalic VK100 Uprioht 112" Brass 2005 5.6 194 155
Vi~no Microfast QR VK404 Pendent 112" Brass 2005 5.6 6 165 Deo.
SPRINKLERS
PIPE AND TYPE OF PIPE Thinwali Threadable' Black
FITTINGS TYPE OF FITTINGS Threaded' Welded Outlets. Mechanical Tees
FLOW ALARM DEVICE MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION
TYPE MAKE I MODEL MIN. SEC.
Existing I I I
N/A I I I
EXPLAIN ANY ALARM PROBLEMS:
ALARM
DEVICES LOW AIR ALARM DEVICE ALARM OPERATED
TYPE MAKE I MODEL PRESSURE PROPERLY
NIA I I SETTING PSI I
YES NO
I
EXPLAIN ANY ALARM PROBLEMS:
CENTRAL MONITORING SIGNALS RECEIVED
ALARM SERVICE LOCATION(S)
TYPE OR PRESSURE
NAME OF REMOTE WATERFLOW SWITCH LOW-AIR OTHER
SERVICE DETECTOR FLOW SUPERVISORY
SUPERVISING LOCATION(S):
STATION
(ON-5ITE)
REMOTE REMOTE NAME OF SERVICE:
MONITORING
ALARM SERVICE
SIGNALING (OFF-5ITE)
PHONE:
OTHER: LOCATION(S):
EXPLAIN ANY ALARM SIGNALING PROBLEMS:
DRY VALVE Q.O.D.
MAKE I MODEL SERIAL NO. MAKE MODEL SERIAL NO.
I I I I I
TIME TO TRIP WATER TRIP POINT AIR TIME WATER ALARM
THROUGH TEST PRESSURE AIR PRESSURE PRESSURE REACHED TEST OPERATED
CONNECTION'" OUTlET U PROPERLY
DRY PIPE MIN. SEC. PSI PSI PSI MIN. I SEC. YES I NO
OPERATING WITHOUT I I I
TEST Q.O.O.
WITH I I I
Q.O.D.
IF NO, EXPLAIN:
OPERATION: 0 PNEUMATIC 0 ELECTRIC 0 HYDRAUliC
PIPING SUPERVISED DYES DNO T DETECTING MEDIA SUPERVISED DYES DNO
DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS DYES DNO
IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN
DELUGE & CiRCUIT FOR TESTING
PREACTION DYES DNO
VALVES
DOES EACH CIRCUIT DOES EACH CIRCUIT MAXIMUM TIME TO
OPERATE SUPERVISION OPERATE VALVE RELEASE OPERATE RELEASE
MAKE MODEL LOSS ALARM
YES I NO YES NO MIN. SEC.
I
LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
FLOOR IFLOWING)
PRESSURE I~p~; I OUTLET INLET I OUTLET FLOW
REDUCING IPSI) IPSI) IPSI) IGPM\
VALVE TEST I I
Ahem Fire Protection
, MEASURED FROM TIME INSPECTORS TEST CONNECTION IS OPENED.
'NFPA 13 ONLY REQUIRES THE 6O-$ECONO LIMITATION IN SPECIFIC SECTIONS.
2
Ahern Fire Protection
HYDROSTATIC: Hydrostallcteslsshall be madeal not less than 200 psi (13.6 hars) for two hours or SO psi (3.4 bars) above static pressure In
excess of 1SO psi (102 bars) for two hours. D;¡¡erential dry-pipe valve clappers shall be left open during test to prevent damage. All
TEST aboveground piping leakage shall be stopped.
DESCRIPTION
PNEUMATIC: Eslablish 4O-psi (2.7 bars) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 hars) in 24 hours. Test
pressure tanks aI nonnal water level and a;r pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 hars) in 24 hours.
ALL PIPING HYDROSTA TICALL Y TESTED AT 2.<::á.. PSI L-Bar) for ~ HRS.
DRY PIPING PNEUMATICALLY TESTED (J YÈS D NO
EQUIPMENT OPERATES PROPERLY DYES DNO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED
FOR TESTING SYSTEMS OR STOPPING LEAKS?
ES DNO
DRAIN READING OF GAUGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION:- PSI <-Bar) CONNECTION OPEN WIDE: - PSI LBar)
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER OTHER EXPLAIN
FLUSHED BEFORE CONNECTION MADE TO SPRINKlER PIPING.
TESTS
VERIFIED BY COpy OF THE CONTRACTOR'S MATERIAL AND TEST
CERTiFICATE FOR UNDERGROUND PIPING. DYES D NO
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKlER PIPING DYES D NO
IF POWDER-DRIVEN FASTENERS ARE USED IN CONCRETE, HAS
REPRESENTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMPLETED?
DYESDNO
BLANK
TESTING
GASKETS
YES DNO
LOCATIONS
IF YES...
WELDING
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING
PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS
QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO ENSURE THAT ALL DISCS
ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL
DIAMETERS OF PIPING ARE NOT PENETRATED?
IF NO, STATE REASON
IF NO, EXPLAIN
NUMBER REMOVED
p1'YES
dYES
DNO
DNO
fð'YES
DNO
SIGNATURES
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
NAME OF SPRINKLER CONTRACTOR
AHERN FIRE PROTECTION, 201 MORRIS COURT - FOND DU LAC, WI 54935
TESTS WITNESSED BY
TITLE
FOR PROPERTY OWNER (SIGNED)