HomeMy WebLinkAboutLetter-Remco (Bathroom heaters) 05115/2001 14: 21 9207250221 REMCO PAGE 02 REM CO ~NTERPRISES t~ MeGa.... Rd. (4'.) 725.6161 H-"", WI 64956 ~fQ 1" ~t ~c~. 1)' .)o~ ,þ 'Pace, Inc. 5-16-2001 Att : -Leo C. Subject: - unit heaters in Morgan Bathrooms Leo - 1 haveøpent coneiderable timeevaluatinq the items listed above. Each and every time 1 visited thiB comple~ these items didn't ring true from sssfety etendpoint. After consultin~ the Dept. of Commerce - Safety and Buildings, I fe~l definite they would llQt certify the two bathroom areás with the heat sources now employed. Three statutes in particular: - 64.09 - 64.21 (S) and 64.22 (3) (c), addres8 suspended units and, the criteria they must meet. ThoBe it~s address the combustion air requirements of gas fired appli~nce8 and it's introduction into the room- the need for t~ ereae they occupied to:l!§ occuDled" - clearances to combustibles and mounting heights, etc. Openable windoWs do not constitute an "on demand" combustion air source a9 dutlined in the Depar~ment8' Chapter 64 guidelines. By introducingemotorized in1ect dampered opening to provide the combustion.8ir requirements for the (30) MBH unit located in the well tr4vele4 open..stairwell serving the first and second floor o. Building # 1 - 1 feel confident ~t ~ n ~ and would meet the intent of the coda. Even by applying up to (1) Air change par hour in whet you describe as a .;old, drafty little room ( bathroom "A" ) - calculation. indicate an electric unit sized to approx. (3) KW which requires onry ~in1m81clearan~~none of the combustion req~irementB which haunt the gas fired unite, would do the jOb with ease. Please be awar. all bathrooms require exhaust at (75) CFM per "fixture" and \Ust be in a continuous run mode while the building is occupied. As I viewed these two areas -~ exhaust or inl,t devices were evident, Thru ~oor inlet grills from the production areas shall be sized at .04" static prQ88Ure drop in conjunction witñtheexñaust requirements of ;;ø~m~ .. R. Remmel - D-1O69-H 05115/2501 14: 21 9207255221 REMCO PAGE 01 REMCO ENTERPRISES 1902 McGan" Rd. (4"')725-6161 N"t!!I'ah. WI 54956 Dept. of Commerce 5-16-2001 Att' - S. Dobratz subject: - Phone earlier today ( Bathrooms and unit heaters) Steve. 1 have Faxed the enclosed to the Contractor involved al\d will be showing my suggested equipment choice in the areas in question when I present the HVAC Alteration drawingS for certification. 'lease be aware, the gas fired unit heaters referred to have already been employed, so drawings ~ n2Ì reflect an "as built" situation. John van Beucken will also be apprised, ae he 1s scheduled to review the drawingS. 1 had discussed this item with him on a prior occasion to make him aware of my concerns and to be BUre and higblite this item for the State inspection group to ~¿LOA? Dick Remmel KRR/FAX ~ M1 UømJ ÝAN b€ ù(!¡k~ ' -- I/u.r '" bA.1 fk IF - osf! þ:G II