HomeMy WebLinkAbout2005-Building
G
OSHKOSH
ON THE WATER
Job Address 3001 S WASHBURN ST
CITY OF OSHKOSH
No
117266
BUILDING PERMIT - APPLICATION AND RECORD
Owner FIRST HORIZON GROUP LIMITED PTNSHP
Create Date
11/14/2005
Designer
Contractor
ELDER-JONES GENERAL CONTRACTOR
Plan 07-93-1005
Category
232 - Alteration Stores & Customer Service
Type
. Building
0 Sign
0 Canopy
0 Fence
0 Raze
Zoning
Class of Const:
Size
FinishediLiving
-----'! Sq. Ft.
-----'! Sq. Ft.
Rooms
Height
0 Ft.
D Projection I
Unfinished/Basement
Bedrooms
Stories
Canopies 0
Garage
-----'! Sq. Ft.
Baths
0
Signs
0
Foundation
0 Poured Concrete 0 Floating Slab
0 Concrete Block 0 Post
0 Pier
0 Treated Wood
. Other
Occupancy Permit Required
Park Dedication
Flood Plain
Height Permit
# Dwelling Units 0
# Structures
0
Use/Nature D80 - Old Navy - Combine spaces D75 and D80 into one tenant space. remodel for this tenant.
ofWork
Plumbing Contractor
UNKNOWN
HVAC Contractor
UNKNOWN???
Electric Contractor
UNKNOWN????
Fees: Valuatio
Plan Approval
$0.00 Permit Fee Paid
$754.00 Park Dedication
$0.00
Issued By:
Date 11/14/2005
Final/O.P. 00/00/0000
D Permit Voided I
Parcelld # 1329420000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature ~~
Date //.~o/./c..ç-
Address
1120 E 80TH ST
Agent/Owner
BLOOMINGTON
MN 55420 - 0000
Telephone Number
952-854-2854
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
~
OJHKOfH
City of Oshkosh
Division ofInspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
October 26, 2005
Robert Tindall
Callison Architechts, Inc
1420 FiftltAve # 2400
Seattle WA 98101-2343
Duane Henderson
Henderson Engineers Inc
8325 Lenexa Dr, Suite 400
Lenexa KS 66214-1654
Felice Arredondo
Prime Retail
217 E Redwing, 20th Floor
Baltimore MD 21202
Site: DD80 /ÕO7r5'
Old Navy Ontlet # 1734
3001 S Wshburn St
Oshkosh WI 54904
For:
Description: Tenant space alterations
Object Type: Bnilding & HV AC Only
Class of Construction: DB - 14,573 sq ft; SprinkIered
Occupancy: M: Mercantile 1 Retail
Maximum No of Occupants: 379
Plan Number: Q8-93-1005
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) 1 Conditions:
mc 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies ofthefirestopping systems
are required to be provided at the time of inspection.
mc 906.11 IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
. mc 1003.2.10 Exit signs are required to be installed per this section
mc 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to meet the performance
requirements ofIBC 1003.2.11.3.
COMM 62.1109 (12) Where counters are provided for sales or distribution of goods or services, at least
one of each type provided shall be accessible.
IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards.
mc 1101.21 ANSI A117.1-308.2 & 3 -Mechanical system controls shall be located a maximurn of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
Page 1 of4
IMC 302.1 The building or structure shall not be weakened by the installation of mechanical systems.
VerifY that structural modifications are completed per calculations and plans submitted and drift
loading is not required to be considered.
Comm 5.34 No person may perform structural welding unless the person holds a registration issued by
Department of Commerce. Provide welders registration numbers for all people doing welding on this
project.
IMC 304.9 Guards. Guards shall be provided where appliances, equipment, fans or other components that
require service are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and
such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. The
guard shall extend not less than 30 inches (762 mm) beyond each end of such appliance, equipment, fan or
component and the top of the guard shall be located not less than 42 inches (1067 mm) above the elevated
surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch-
diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the
International Building Code. VerifY compliance with this code section
IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment and
appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877
mm), such access shall be provided by a permanent approved means of access, the extent of which shall be
ftom grade or floor level to the equipment and appliances' level service space. Such access shall not
require climbing over obstructions greater than 30 inches (762 mm) high or walking on roofs having a
slope greater than 4 units vertical in 12 units horizontal (33-percent slope).
IMC 306.6 Sloped roofs. Where appliances are installed on a roof having a slope on units vertical in 12
units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above
grade at such edge, a level platform shall be provided on each side of the appliance to which access is
required by the manufacturer's installation instructions for service, repair or maintenance. The platform
shall not be less than 30 inches (762 mm) in any dimension and shall be provided with guards in
accordance with Section 304.9.. VerifY compliance with this code section
IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
ftom any hazardous or noxious contaminant such as vents, chinmeys, plumbing vents, streets,-alleys,
parking lots and loading docks.
IMC 405.1 Mechanical ventilation systems shall be provided with manual or automatic controls that will
operate such systems whenever the spaces are occupied. Air conditioning systems that supply required
ventilation air shall be provided with controls designed to automatically maintain the required outdoor air
supply rate during occupancy.
IECC 803.3.3.3 Off-hour controls. Each zone shall be provided with thermostatic setback controls that
are controlled by either an automatic time clock or programmable control system.
IFGC 401 /Comm 65.0400 All gas piping and gas piping installations shall comply with NFP A 54,
National Fuel Gas Code.
IFGC 619.2 Support. Suspended-type unit heaters shall be supported by elements that are designed and
constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of
noncombustible material.
IFGC 619.4 Clearance. Suspended-type unit heaters shall be installed with clearances to combustible
materials of not less than 18 inches (457 mm) at the sides, 12 inches (305 mm) at the bottom and 6 inches
(152 mm) above the top where the unit heater has an intemal draft hood or I inch (25 mm) above the top
of the sloping side of the vertical draft hood. Where the flue gases are vented horizontally, the 6-inch (152
mm) clearance shall be measured ftom the draft hood of vent instead of the rear wall of the unit heater.
Clearances for servicing all unit heaters shall be in accordance with the manufacturer's installation
instructions. Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with
such clearances in accordance with their listing and the manufacturer's instructions.
.
'.
.
It\hriwm\2005 Comm Plan Review\'Q7-93-IO()5 3001 S Wshbum $1 IIV"C & BI.DG.duç
Page20f4
Comm 161 NEC This plan review does not inclnde a complete review of electrical plans. Please note
there appears to be conflicting information in mechanical and electrical plans as to voltage of mechanical
equipment, and voltage available. (Based on riser diagram it would appear that 480 volts is not available,
however equipment wiring schedule list 480 volt equipment) Additionally there may be an issue with
grouping requirements for switchboard disconnects base on review of riser diagram indicating the
disconnects are not grouped. Please contact Kevin Benner - Electrical Inspector (920) 236-5046 for
additional information on this issue.
Comm 80 This plan review does not include plumbing. Prior to installation of plumbing, plans and
calculations are required to be submitted and approved if required by Comm 82.20. (greater than 16 piumbing
fixtures, or specific item listed in Table 82.20-2)
MUN 30 - This review does not include review for exterior signage, which will require separate review
by the planning department prior to permit issuance for exterior sigoage. Contact David Buck - Associate
planner (920) 236-5062 for additional information on sigo permit submittal requirements
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be sigoed and sealed in accordance with
Comm 61.31(1).
SUBMIT:
MUN 30-35 (1)(5) All rooftop and ground level mechanical equipment and utilities shall be fully screened
ftom view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally mc 1608.8 Roof projections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in
accordance with Section 1.8 of ASCE 7. Provide calculations for drift loading - NO HV AC PERMIT
WILL BE ISSUED PRIOR TO SCREENING PLANS BEING APPROVED
IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Sheet M4-0
provides only a suggested layout for sprinkler system. - Submit plans and calculations for fire sprinkler
modifications.
Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. Please submit lighting work sheets.
IECC 503.3.3.1 [Comm 63.0503(2)(1)] Balancing and documentation of the HV AC system shall conform
to the IMC. Balancing report required to be submitted prior to final occupancy being allowed.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
H;\brian¡¡'2005 Comm I'IGn Reviow,'Q7-93-tOO5 3001 S W,hborn 51 HVAC & BLDGdoç
Page30f4
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component. C
this correspondence may be made to me at the number listed below or the address on this letterhead.
BnanNoe
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30A.M and 12:30 A.M to 1:30 P.M.