HomeMy WebLinkAbout0116955 H
e
OSHKOSH
ON THE WATER
Job Address 460470480 N MAIN ST
CITY OF OSHKOSH
No
116955
HVAC PERMIT. APPLICATION AND RECORD
Owner
BENT BLOCK OSHKOSH LLC
Create Date 09/30/2005
Plan Q5-86-0905-H
Contractor
CONDON TOTAL COMFORT
Category 510 -Ind. & Comm-Heating & Ventilating
Fuel
1 I Oil
1 1 Solar
1 I Solid
System
1,(1 Gas
I?] New
1,(1 Electric
n Replace
n Other
~ Forced Air
1 1 Electric
~ Vent
U Radiant
1 I HotWater
U Steam
1 1 Suppl.
U AlC I
1 1 Con. Burner I
e ) Not Applicable
Heat Loss
. As Approved
. As Per Plan
e) Chimney B
e ) Existing
. Direct Vent
Chimney Type K) Chimney A
BTU Rate
e ) Variable
e ) Not Applicable
e ) Other
Value
Value
Use/Nature 80 N Main St / Oshkosh PC - Tenant space build out as per plans - install duct work on exisilng equipment, and install 3 exhaust fans.
ofWork
Fees: Valuation
$1,650.00
Plan Approval
$0.00
Penmit Fee Paid
$30.50
Issued By:
Date 10/25/2005
D Permit Voided I
Parcelld # 0400940000
In the performance of this work, I agree to perform all work pursuant to rules governing tI1e described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform tI1e work
described in tI1is permit application witl1in an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
Agent/Owner
Address
PO BOX 184
RIPON
WI 54971 -184
Telephone Number
920-748-5050
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
-----'"
(t)
QfHKQfH
O","E WATER
City of Oshkosh
Division of Inspection Services
215 Church Avenue
POBox 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
October 25, 2005
Arthur Warren
Condon Total Comfort Inc
II Blackburn St
Ripon WI 54971
Peter Jungbacker
Bent Block Oshkosh LLC
377 City Center
Oshkosh, WI 54901
Site:
Oshkosh PC
480 North Main St
Oshkosh WI 54901
For:
Description: Interior Alterations
Object Type: HV AC only
Class of Construction: DIB - 4230Ft.;
Occupancy: B Business I Office
Maximum No of Occupants: 24
Plan Number: Q5-86-0905-H
Sprinklered
The submittal described above has been reviewed for confonnance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
mc 711.3 Any penetrations offire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated.
mc 1101.2 / ANSI AI17.1-308.2 & 3 -Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corom 61.31(1).
SUBMIT:
. IECC 503.3.3.7 [Comm 63.0503(2)(1)] Balancing and documentation of the HV AC system shall conform
to the IMC. Balancing report required to be submitted prior to final occupancy being allowed.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
¡¡'\briann'2005 CumIn Plan Ro,iow,',Q5-8b-O905-I i 4&0 N Main 5t HVAC Oniy.do,
Page 1 of2
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Re~y,
~~
Building Systems Consultant
(920)236-5051 Monday-Friday 7:30 A.M. to 8:30A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
230.00
230.00
0.00
Ij,\bri.nn\20û5 Comm Phm Roviow"Q5-86-0905-U 480 N Main S: ¡IVAC Only.doc