HomeMy WebLinkAbout0116815-Electric
~
OSHKOSH
ON THE WATER
Job Address 401 W 33RD AVE
CITY OF OSHKOSH
No
116815
ELECTRIC PERMIT - APPLICATION AND RECORD
Contractor
EXCELLENCE ELECTRIC
0 Change
0 Temp
Owner SMET INVESTMENTS LLC Create Date 10/13/2005
Category 642 - Commercial-New Building Wiring Plan
ON/A Type 0 Overhead ~derground
Circuits 0 Fixtures ~
Switches 0 Receptacles ~
Service . New
Volts 277/480
Amps 1200
Appliances
Use/Nature of INDI New power wirng for 20,060 sf one story office building. Low voltage wiring by others. Job # 8408
Work
Fees: Valuation
$105,287.00
Plan Approval
$0.00
Permit Fee Paid
$502.00
Issued E\y:
Date 10/17/2005
0 Permit Voided I
Parcelld# 1413650200
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit applicetion within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature¡qfl ~
Date
Address
321 E MAIN ST
AgenUOwner
LITTLE CHUTE WI 54140 - 78
Telephone Number 920-687-2442
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Job Address ,401 W 33RD AVE
Ownei SMET INVESTMENTS LLC
Electric Permit Work Card
Permit Number 116815 Create Date 10/13/2005
Contractor EXCELLENCE ELECTRIC
Category 642 - Commercial.New Building Wiring
Service b New 0 ChangeO Temp 0 N/A I Type 0 Overhead
Volts 277/480~ Circuits 0
. Underground Q N/A
.-J
Fixtures
Amps
1200
Switches
Receptacles
Fee
$502.00 0
Value
$105,287.00
Use/Nature
of Work
l
[ = ~.OOO . ~ - - ""'"". ~ -~ ."~ ~ oM' '00 . -
Appliances
Inspections:
Date 10/1312005
Type Underground
Inspector Kevin Benner
approved'w/cond.
Repiace the GRS elbows with PVC
Discussed with Don Hayes from the E.C.
Datemme requested: 10/12/2005 01:50 PM
Access:
Notice Type:
Phone Number: 687-2442
Ready DatelTime: 1 0/13/2005 ~1.=°0 AM Requested by:
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC Rob
Date 10/18/2005
Type Underground
Inspector Kevin Benner
not approved
Request Line - underground inside building - there next couple days
All of the conduits were backfilled when I got on site. No one was on site.
DatelTime requested: 10/17/2005 01:29 PM
Access:
Notice Type:
Phone Number: 687-2442
Ready DatelTime: 10/17/200501:29 PM Requested by:
~--~
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC-Rob
Job Address. 401 W 33RD AVE
Owne~ SMET INVESTMENTS LLC
Electric Permit Work Card
Permit Number 116815 Create Date 10/13/2005
Contractor EXCELLENCE ELECTRIC
Category 842 - Commercial-New Building Wiring
Circuits
I Type Q Overhead
0
. Underground Q N/A
Service b New
Volts 277/480
Amps ~
0 ChangeO Temp 0 N/A
Fixtures
Switches
Receptacles
Fee
$502.00 0
Value
$105,287.00
Appliances
L-
_-l
Use/Nature
of Work
"" - ,0-.-. ~'".~... "" ". .."'~. ~ .'-~"' ~ _. ~. MOO '
Inspections:
Date 11/21/2005
Type Rough In
Inspector Kevin Benner
not approved'
I~-
DatelTime requested: l1!1_812005 10:24 AM Notice Type:
Access:
Eric Heiptas is the Foremean on site -..-
Ready DatelTime: 11/2.1/2005 07:20 AM Requested by:
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Phone Number:
EXCELLENCE ELECTRIC Rob Hophensbe
Date 11/23/2005
Type Re Rough In
Inspector Kevin Benner
approved w/cond.
Request Line
Discussed ENT bending radius with Eric (2nd time)
DatelTime requested: ~.?~~~005 02:18 PM
Access:
Open - wants Wednesday afternoon.
Ready DatelTime: lll.?~2005 12:00 PM Requested by:
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Phone Number: 540-4870
EXCELLENCE ELECTRIC-Eric
Job Address. 401 W 33RD AVE
Owne; SMET INVESTMENTS LLC
Electric Permit Work Card
Permit Number 116815 Create Date 10/13/2005
Contractor EXCELLENCE ELECTRIC
Category 842 - Commercial-New Building Wiring
0 ChangeO Temp 0 N/A I Type 0 Overhead
Circuits 0
Service b New
Volts 277/480
Amps 1200
. Underground Q N/A .-------J
Fixtures 0
Switches -~
Receptacles 0
Fee $502.00 0
Value
$105,287.00
l
Appliances
Use/Nature
of Work
IND\ New power wirng for 20,060 sf one story office building. Low voltage wiring by others. Job # 8408
-,
Inspections:
Date 12/16/2005
Type Service
Inspector Kevin Benner
not approved
Request Line - wants Friday AM
AFWL, AiC from XFMR? (65KAIC MCB), GFP Test, Grounding Bonding Jumper.
Datemme requested: 12/15/2005 08:08 AM
Access:
Notice Type:
Phone Number:
Ready DatelTime: ~16/2005 07:00 AM Requested by:
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC-Eric
Date 12/21/2005
Type Re Servi~ Inspector Kevin Benner
approved w/cond.
Eric Stated the AiC is 35K. He said the GFP test can be conducted after the service is energized and the
factory settings are at the maximum settings,
Eric stated that the vio.'s have been corrected snd the GFP tests are scheduied for Thursday
12/22/05.Approved to energize
Faxed to WPS 12/21/05
DatelTime requested: 12/19/2005 07:58 AM Notice Type:
Access:
Phone Number: 920-540-4870 Eric
Ready DatelTime: 1,?/19/2005 07:58 AM Requested by:
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRiC Eric
Job Address. 401 W 33RD AVE
Owne"r SMET INVESTMENTS LLC
Electric Permit Work Card
Permit Number 116815 CreateDate 10/13/2005
Contractor EXCELLENCE ELECTRIC
Category ~.:..Ç-",!,mercial-New Building Wiring
0 ChangeO Temp 0 N/A
I Type 0 Overhead
. Underground 0 N/A
Service b New
Volts 277/480
Amps 1200
Circuits 0
Fee
$502.00 0
Fixtures 0
Receptacles 0
Value $105,287.00
Switches
Appliances
Use/Nature
of Work
INDI New power wirng for 20,060 sf one story office building. Low voltage wiring by others. Job # 8408
Inspections:
Date 01/03/2005
Type Abv Ceiling
Inspector Kevin Benner
approved w/cond.
Request Line (rec'd without permit# or address) - wants late Friday afternoon.
Reviewed the following with Troy K. : open boxes for sensor wiring, whios hanging for recessed cans and
emergency luminaires not installed, acrylic troffers ceiling clips notinstalled properly, MC cable assemblies not
secured to the grid in southwest office
DatelTime requested: ~~9/2005 03:03 PM
Access:
Notice Type:
Phone Number: 540-4870
Ready DatelTime: 12/30/200502:00 PM Requested by:
--
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC
Date 01/19/2006
Type Final
Inspector Kevin Benner
not approved
REQUEST LINE / HOPEFULLY INSPECTION WILL BE FRIDAY
WH disc., NFPA 72 10 req., panel schedules, em its on locai circuit, panel cover in conf. rm, ex!. em Its do not
function, no em It illumination in the back room and the northeast corner 0 f the office area. Reviewed with Eric
from the E.C.
DatelTime requested: Q:I/18/2006 02:38 PM
Access:
Notice Type:
Phone Number: 540-4870
Ready DatelTime: 01118/200602:38 PM Requested by:
--
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
ERIC
~Jb Addr~ss 401 W 33RD AVE
Owner SMET INVESTMENTS LLC
Electric Permit Work Card
Permit Number 116815 CreateDate 10/13/2005
Contractor EXCELLENCE ELECTRIC
Category 642 - Commercial-New Building Wiring
Service b New 0 changeO Temp ON/A I Type 0 Overhead . Underground ON/A
Volts 277/480 Circuits 0 Fixtures 0
Amps 1200 Switches Receptacles ~
Fee $502.00 0 Value $105,287.00
Appliances
I
Use/Nature
of Work
lí'JB\New power wirng for 20,060 sf one story office building. Low voltage wiring by others, Job # 8408
Inspections:
Date 12/16/2005
Type Service
Inspector Kevin Benner
not approved
Request Line - wants Friday AM
AFWL, AIC from XFMR? (65KAIC MCB), GFP Test, Groundin9 Bonding Jumper.
DatelTime requested: 12/15/2005 08:08 AM
Access:
Notice Type:
Phone Number:
Ready Date/Time: 12/16/200507:00 AM Requested by:
..~-
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC-Eric
Date 12/21/2005
Type Re Service
Inspector Kevin Benner
pproved w/cond.
Eric Stated the AIC is 35K. He said the GFP test can be conducted after t is energized and the
factory settings are at the maximum settings.
Eric stated that the vio.'s have been corrected snd the GFP tests are scheduled for Thursday
12/22/05.Approved to energize
Faxed to WPS 12/21/05
DatelTime requested: 12/19/2005 07:58 AM
Access:
Notice Type:
Phone Number: 920,540-4870 Eric
Ready DatelTime: 12/19/2005 07:58 AM Requested by:
,~-
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
EXCELLENCE ELECTRIC Eric
12I20~2005 TIlE 22: 35 FAI 920 687 2445 EXCELlJINCE EllicrRIC
~OOl/001
/PÃ Excellence
\...V ELECTRIC Jnc.
FaK CcMr
To: Kevin Benner
Fax: 920-236-5084
Phane:
Reo GE Oit and Gas
From: Rob Hopfensperger
Pages; 1
Date: December 20, 2005
CC:
To: Kevin Benner, City of OShkosh Eleclricallnspector
RE: 12O0amp service Equipment at GE Oil and Gas
Kevin,
In talking with GE technical support, I have been assured that the trip settings: including the ground fault setting
can be programmed after the unit Is energized. The trip functions are set to maximum as default settings and can
be adjusted aflerthe bleaker is energized, Final trip settings and testing will be done on Thursday, December 22,
A copy of the final settings and trip test will be available fQr your review anytime after Friday, December 3D"'.
Thank you for your cooperation in this matter.
Rob Hopfensperger