RE:
FIRE PROTECTION SYSTEM INSTALLATION
PACUR, INc.
3555M6sERSTREET
OSHKOSH, WISCONSIN 54901
AHERN FIRE PROTECTION CONTRACT No. 490363
Dear Brian:
Enclosed is a copy of the Contractor's Material and Test Certificates covering the above-referenced
Fire Protection System Installation for your fileSe
'\téry truly yours,
AHERN FIRE PROTECTION
4d3JF~
JeffR. Batterman
Service Superintendent
JRB/ksj
LCITYO9-27-".DOC
An Equal Opportunity Employer
AHERN FIRE PROTECTION
Contractor's Material and Test Cemfiêäte for Aboveground Piping
PROCEDURE
Upon completion ofwcrlc, inspection and tests shall be made by the cont_OI's representative and witnessed by an owner's representative. All detects shall be
corrected and system left in servica before contraclor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving euthorities, owners, and _or. «is understood the
:::'~':"":'::o"'::":'; :'=':r~~':=- prejudices any claim against """""""'r for fauBy material, poer_nship, or failure to complywRh appmving
PROPERTY NAME Pacur, Inc. AFP Contract #: 490363 DATE: August I, 2OOS
PROPERTY ADDRESS 3555 Moser Street Oshkosh, WI 54901
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
1. City of Oshkosh (Building Inspector -- Brian Noe)
2. Oshkosh Fire Department (Battalion Chief - Greg Piper)
3.
4.
ADDRESS
Plans 1. 215 Church Avenue -- PO Box 1130 -- Oshkosh, WI 54901
2. 101 Court Street -- OshkoSh, WI 54901
3.
4. /
INSTALLATION CONFORMS TO ACCEPTED PLANS ~ES DNO
EQUIPMENT USED IS APPROVED ES DNO
IF NO, EXPLAIN DEVIATIONS
/
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TQLOCATION ¡ø'YES DNO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
INSTRUCTIONS IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: rivES
Item No.'s2 & 3"'" I. SYSTEM COMPONENTS INSTRUCTION ~g
be "'<Wa>ded by AFP 2. CARE AND MAINTENANCE INSTRUCTIONS DYES
at,'oseoattime.
3. NFPA 25 DYES NO
LOCATION OF SUPPLIES BUILDINGS
SYSTEM System #2
MAKE MODEL YEAR OF K- QUANTITY TEMPERATURE
MANUFACTURE FACTOR RATING
VikiM Microfasl M OR VK3O0 UDriDhl11T Bronze 2005 5.6 12 155 Oea.
Vi~nn M"lCmfast M OR VK3O2 Pendenlln' Chrome 2005 5.6 50 155 Oea.
SPRINKLERS
PIPE AND TYPE OF PIPE Uahtwall Non-Threadable' Thinwall Threadable
FITTINGS TYPE OF FITTINGS Grooved' Threaded' Welded Outlets. Mechanical Tees
FLOW ALARM DEVICE. .. MAXIMUM TIME TO OPERATE
. THROUGH TEST CONNECTION
TYPE I MAKE MODEL MIN. I SEC.
Existing I I I
N/A I I I
EXPLAIN ANY ALARM PROBLEMS:
ALARM
DEVICES LOW AIR ALARM DEVICE PRESSURE ALARM OPERATED
TYPE I MAKE MODEL PROPERLY
I I SETTING PSI I
N/A YES NO
I
EXPLAIN ANY ALARM PROBLEMS:
CENTRAL MONITORING SIGNALS RECEIVED
ALARM SERVICE LOCATION(S)
TYPE OR PRESSURE
NAME OF REMOTE WATERFLOW SWITCH LOW-AIR OTHER
SERVICE DETECTOR FLOW SUPERVISORY
SUPERVISING LOCATION(S):
STATION
(ON-SITE)
REMOTE REMOTE NAME OF SERVICE:
MONITORING
ALARM SERVICE
SIGNALING (OFF-SITE)
PHONE:
OTHER: LOCATION(S):
EXPLAIN ANY ALARM SIGNALING PROBLEMS:
DRY VALVE I Q.O.D.
MAKE MODEL SERIAL NO. I MAKE MODEL I SERIAL NO.
I I I I I
TIME TO TRIP WATER TRIP POINT AIR TlMEWArER ALARM
THROUGH "TEST AIR PRESSURE REACHEOTEST OPERATED
CONNECTION'" PRESSURE PRESSURE OUTLET ,> PROPERLY
DRY PIPE MIN. I SEC. PSI PSI PSI MIN. SEC. YES NO
OPERATING WrTHOUT I I I
TEST 00.0.
WrTH I I I
00.0.
IF NQ, EXPLAIN:
OPERATION: 0 PNEUMATIC 0 ELECTRIC 0 HYDRAULIC
PIPING SUPERVISED DYES DNO I DETECTING MEDIA SUPERVISED DYES DNO
DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS DYES DNO
IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN
DELUGE & CIRCUIT FOR TESTING
<>REACTION ..- DYES ONO
VALVES
DOES EACH CIRCUIT DOES EACH CIRCUIT MAXIMUM TIME TO
OPERATE SUPERVISION OPERATE VALVE RELEASE OPERATE RELEASE
MAKE MODEL LOSS ALARM
YES I NO YES I NO MIN. SEC.
I 1
LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
FLOOR (FLOWING)
PRESSURE INLET 1 OUTLET INLET I OUTLET FLOW
REDUCING (PSI) IPS) tPS) IPS) IGPM)
VALVE TEST I I
Ahem Fire Protection
, MEASURED FROM TIME INSPECTORS "TEST CONNECTION IS OPENED.
, NFPA 13 ONLY REQUIRES THE 6O-SECONO LIMITATION IN SPECIFIC SECTIONS.
2
Ahem Fire Protection
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) abcve static pressure in
excess of 150 psi (10.2 bars) for two hours. Oifferential doy-pipe valve clappers shall be left open during test to prevent damage. All
TEST a_round piping leakage shall be slopped.
DESCRIPTION
~ Establish -4G-psi (2.7 bars) air pressure and measure drop, which shall not excaed 1-112 psi (0.1 bars) in 24 hours. Test
pressure tanks at normal water level and air pressure an,! measure ak pressure drop, which shall no! exceed 1-112 psi (0.1 bars) in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT SI L-J!ar) for _HRS. IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED DYES œ1iIo .£.-
EQUIPMENT OPERATES PROPERLY !EfYES DNO ¡V""'T'-C$~
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SlliC TE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED
FO TESTING SYSTEMS OR STOPPING LEAKS?
YES DNO
DRAIN READING OF GAUGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION:--?-Z-PSI <---Bar) CONNECTION OPEN WIDE:.s:.G- PSI LBar)
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER OTHER EXPlAIN
FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING.
TESTS
~~~~II~~:;E ~'bl;t UO:D~~~~g~~~~;~~S MATERIAL AND TEST 0 YES Œt1i'o
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING 0 YES IDO
IF POWDER-DRIVEN FASTENERS ARE USED IN CONCRETE, HAS
REPRESENTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMP¡j~~~?~O
BLANK
TESTING
GASKETS
NUMBER USED
LOCATIONS
WELDED PIPING
YES DNO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING
PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
WELDING
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS
QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO ENSURE THAT ALL DISCS
ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL
DIAMETERS OF PIPING ARE NOT PENETRATED?
SIGNATURES
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
NAME OF SPRINKLER CONTRACTOR
AHERN FIRE PROTECTION, 201 MORRIS COURT FOND DU LAC, WI 54935
TESTS WITNESSED BY
TITLE
FOR PROPERTY OWNER (SIGNED)
a.-1\~!i.J.; ,.vj
IF NO, EXPLAIN
rI Or! «S"e c/
NUMBER REMOVED
YES
DNO
ø<eS
~
DNO
DNO
ES
DNO
IF NO, EXPLAIN
DATE
3