HomeMy WebLinkAboutLetter 7/20/05-Damage Assessment Larson Engineering of Wisconsin 1500 Casaloma Drive, Suite 302 Appleton, Wisconsin 54913 - 8219 USA T 920.734.9867 F 920.734.9880 WEB www.larsonengr.com/wì.htm œ Larson JUL 2 1 2005 Wednesday, July 20, 2005 Allyn Danoff Oshkosh Building Inspector Room 205, City Hall Oshkosh, WI 54901 Re: 555 Division 81. Fire Damage Larson Project #: 31050276.000 Dear Allyn: At the request of Matt Everett of Paul Davis Restoration, I inspected fire damage at 555 Division Street, to determine if the remainder of the building could be re-occupied by the adjoining tenants. The fire was contained primarily in one unit, but the fire had crossed the fire wall via a continuous roof vent. The fire then spread along the top of the adjoining attic area, to approximately 15 to 20 feet from the fire wall. 2 trusses were damaged by the fire and will need to be repaired or replaced, while the remaining trusses will require a more detailed inspection during repairs to determine their condition. The structural condition of the adjoining building (across the fire wall from the fire) is in acceptable condition to occupy by the tenants, and poses no risk to the occupants at this time. Even though the trusses have sustained damage, there is sufficient redundancy in the roof structure to maintain the integrity of the building during the summer months when roof loads are at a minimum. I see no reason at this time to restrict access to this part of the building. Since repairs are proceeding immediately, the contractor will be on site, and additional safety issues will be addressed on an as needed basis, per normal construction practice. Please contact me if you require further assistance in this matter. Sincerely, Larson Engineering of Wisconsin ,,'~ëöÑ~;-', .'~' """"",11 '; :,,-* :,,"DAVID D, """ * ". : :' KAMPE- ': Ct: : "t : E-28981 : W . . ';Xl:, OSHKOSH,: /J,¡ : ",O~"" WIS. "",~.: . '. "" ION A\.. ..' .y-iDlòi- ~ David D. Kampe P.E.