Job Address 465 N MAIN ST
CITY OF OSHKOSH
No
116324
HVAC PERMIT -APPLICATION AND RECORD
Owner
STAPEL PROPERTIES I LLC
Create Date 09/16/2005
Plan 02-75-0905
Contractor GARTMAN MECHANICAL SERVICES
I I Oil
Fuel 1,11 Gas
System [7] New I
~ Forced Air U Radiant
I I Electric I I HotWater
Chimney Type K) Chimney A e ) Chimney B
Heat Loss . As Approved e ) Existing
BTU Rate . As Per Plan e ) Variable
Category 510 - Ind. & Comm-Heating & Ventilating
I I Solid
I I Electric
n Replace
I I Solar
n Other
U AlC I ~ Vent
I I Can. Burner I
. Not Applicable
U Steam
I I Suppl.
e) DirectVent
e ) Not Applicable
e ) Other
Value
Value
Use/Nature 9 Church Ave - Install kitchen exhaust system as per plans. Hood to be run when any cooking equipment is in use.
ofWork
Fees: Valuation
$17,835.00
Plan Approval
$0.00
Permit Fee Paid
$284.00
Issued By:
Date 09/16/2005
D PenmitVoided I
Parcelld # 0700220000
In the perfonmance of this work, I agree to perfonm all work pursuant to rules goveming the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the penmit applicant to contact the easement
holder(s) and to secure any necessary approvais before starting such activity.
Signature
Date
AgenUOwner
Address
PO BOX 2284
OSHKOSH
WI 54903 - 2264 Telephone Number
(920) 231-5530
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
-
City of Oshkosh
Division ofInspe<:tion Services
215 Chu;ch Avenue
PO Box 1130
Oshkosh WI 54903.1130
www.ci.oshkosh.wi.us
~
OJHJ<OfH
ON THE WATER
September I~, 2005 -
Keith Paul
GMS Inc
520 W South Park Ave.
Oshkosh, WI 54902
James Staple
Staple Properties LLC
427 N Main St
Oshkosh, WI 54901
Plan Number: Q2-75-0905
Site:
Pearson's Pig & Ponltry
9 Church Ave
Oshkosh WI 54901
For:
Description: Kitchen Exhanst Hood
Object Type: HVAC only
Class of Construction: nm - 938 Sq Ft.; Unsprinklered
Occupancy: M: Mercantile I Retail
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittaJ has been CONDITIONALLY APPROVED. The owner, as derIDed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
.
IMC 304.1 Equipment and appliances shall be installed as required by the terms of their approval, in
accordance with the conditions of the listing, the manufactures instructions and this code. Manufacture's
specifications and listing require the Southern Pride smoker to be installed under a vent hood. THIS
HOOD IS REOUIRED TO BE USED AT ALL TIME THE SMOKER IS BEING OPERATED! Plan
submittal indicates that the smoker would be vented independently and the hood only used when
loading and unloading the smoker - THIS IS NOT PERMITTED - unless additional listing
documanetaion is provided that indicates the listing of the product will allow for this. Additionally the
proposed venting of the smoker using a 2 inch stainless steel vent must be installed per the listing and
installation instructions.
IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
from any hazardous or noxious contaminant such as vents, chimneys, plumbing vents, streets, alleys,
parking lots and loading docks.
IMC 506.3.9 Clean outs and other openings. Grease duct systems shall not have openings therein other
than those required for proper operation and maintenance of the system. Any portion of such system
having sections not provided with access from the duct entry or discharge shall be provided with cleanout
openings. Cleanout openings shall be equipped with tight-fitting doors constructed of steel having a
thickness not less than that required for the duct. Doors shall be eqnipped with a substantial method of
latching, snfficient to hold the door tightly closed. Doors shall be designed so that they are operable
without the nse of a tool. Door assemblies, including any frames and gasketing, shall be approved
for the purpose, and shall not have fasteners that penetrate the duct. Listed and labeled access door
assemblies shall be installed in accordance with the terms ofthe listing.
.'.oSIIKOSIiMISFS\USFIW.hnano.,OÜ5 Comm Pian Rev;c,,","Q2-7;'()9û;" Ch",ch ",yc. IIVAC Only.dn,
Pagelof3
.
IMC 506.3.10 Horizontal c1eanouts. Cleanouts located on horizontal sections of ducts shall be spaced
not more than 20 feet (6096 mm) apart. The c1eanouts shall be located on the side of the duct with the
opening not less than 1.5 inches (38 mm) above the bottom of the duct, and not less than 1 inch (25 mm)
beJow the top of the duct. The opening minimum dimensions shall be 12 inches (305 mm) on each side.
Where the dimensions ofthe side ofthe duct prohibit the cleanout installation prescribed herein, the
openings shall be on the top of the duct or the bottom of the duct. Where located on the top of the duct, the
opening edges shall be a minimum of I inch (25 mm) from the edges of the duct. Where located in the
bottom of the duct, cleanout openings shall be designed to provide internal damming around the opening,
shall be provided with gasketing to preclude grease leakage, shall provide for drainage of grease down the
duct around the dam, and shall be approved for the application. Where the dimensions of the sides. top or
bottom of the duct preclude the installation of the prescribed minimum-size c1eanout opening. the cleanout
shall be located on the duct face that affords the largest opening dimension and shall be installed with the
opening edges at the prescribed distances from the duct edges as previouslv set forth in this section.
IMC 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet (3048 mm)
horizontally from parts of the same or contiguous buildings, adjacent property lines and air intake openings
into any building and shall be located not less than 10 feet (3048 mm) above the adjoining grade level. As
indicated in plan submittal this will require closing some existing windows.
IMC 507.9 A type I hood shall be installed with a clearance to combustibles of not less than 18 inches.
Exception: Clearance shall not be requiredfrom gypsum wallboard attached to noncombustible
structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed
between the hood an the gypsum wall-board over an area extending not less than 18 inches in all
directions from the hood.
As per plan a wall constructed of steel studs with gypsum board and stainless steel covering will be
installed behind the hood.
IMC 507.12 The inside lower edge of canopy-type commercial cooking hoods shall overhang or extend a
horizontal distance of not less than 6 inches beyond the edge of the cooking surface.
IMC 509.1 An approved automatic fire suppression system complying with the mc and IFC is required
for this hood installation.
mc 904.11.2 System Interconnection The Interconnection of the fire suppression system shall
automatically shut down the fuel or elec1rical power supply to the cooking equipment. The fuel and
e1ec1rical supply reset shall be manual.
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shoJI be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm61.31(1),
MUN 30-35 (1)(5) mechanical equipment and utilities shall be fully screened from view of any street or
residential zoning dis1rict. EF-l Exhuast unit is required to be painted to match the building - Contact
David Buck - Associate planner (920) 236-5062 for additional information on screening requirements.
.
.
"\OSTIKOSTIMISrS\I;SFRS'Jm""n\2005 Comm Plan Revlew,;'Q2-7õ-O<JO5 9 Chucd, Ave. HVAC Only.d,,'
Page 2 of3
SUBMIT:
IECC 503.3.3.7 [Comm 63.0503(2)(1)) Balancing and documentation of the HV AC system shall conform
to the IMC, Balancing report required to be submitted prior to final occupancy being allowed.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this ietter shall be on-site during construction. All pennits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
_Res~
~æc
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
230.00
230.00
0,00
'."()STIKOSlIMJSFS',USFf<S'.briann'.2QOj Comm Plan Review,,'Q1-75.Q<)Qj 9 Chard, 'we TIVAC Oniy.doe
Page30f3
, Buildings, HVAC, Compliance Statement OCT 242005
This form is required to be submitted by the supervising professional (architect, engineer, HVAC '!..esig~er o~ ~~ctr\Çal
designer) observing construction of projects within buildings with total areas 50,000 cubic feet oæç'ìji:¡,rr.~i:!ibl¡,áat1ers
(Comm 50.1 OfComm ~1.50). Failure to submit this form may result in penalties as specif¡¡tJ~~íf.8Nrr1~~~~~J1ENT
61.23 and/or local ordinances,
GenerallrìstructÙms: Prior to the initial occupancy of new buildings or additions and the final occupancy of
altered existing buildings, submit this completed and signed form to:
. The municipal building inspection office and
. Safety and Buildings, 10541N Ranch Road Hayward, Wi. 54843
Personal information you provide may be used for secondary purposes [Privacy Law, s. 15,04 (1)(m)].
1. PROJECT INFORMATION: Please fill in the following with inforn¡¡ation J!!?m YOUrPI~pr~~
TransactionlDNumber./ ~5'SðJtS' /)9'0 /?7/L¿'¿;..r/
Site Number /' '~ {j
Site location (number & street) ~ Cdá:_J""o 1¿.J e -/ / }, j
~ity D Village DTown of .á--dR¿:::>.:s-. Countyof/A/ )/lIl<e)!)@C)-O
2. PURPOSE OF THIS STATEMENT: (Check Box A, B, C, or D to indicate purpose and complete any ¡(¡her
applicable boxes and information. Attach additional pages if nece~sary.) . ---
Check those which apply: D Building Object ID # VAC Object 10 #
D Lighting Object ID# ~""'...-% -OJ!¿P-':!;
0 Partial Completion
A) 0
Description of Portion Completed
Statement of Substantial Compliance
To the best of my knowledge, belief, and based on onsite observation, construction of the following building and/or
HVAC items applicable to this project have been completed in substantial compliance with the approved plans and
specifications.
0 BUILDING/LIGHTING ITEMS
1. Structural system Including submittal and erection of all building components
(trusses, precast, metal building, etc.)
2. Fire protection systems (sprinklers, alàrms, smoke detectors) designed, Installed,
end tested (including forward flow on back flow devices) by appropriately registered
professionals
3, Shafl and stairway enclosure
4, Exits including ex" and directional lights -/
5. Fire-resistive construction, enclosure of hazards, fire walls, labeled doors, class of ~VAC ITEMS
construction, fire stopped penetrations
6, Sanitation system (toilets, sinks, drinking facilities) 1, HVAC system inciuding flnal lest
7, Barrier-free including Comm 18 elevators and lifts 2. All conditions of HVAC plan approval and
8. Energy envelope requirements applicable variances
9. All conditions of buiidlng plan approval and applicable variances
The following Items are not in compliance and must be addressed:
10, Exteriorlighling & control requiremenls
11, Interior lighting & control requirement$
12, All conditions of lighting plan approval
and applicable variances
B) 0 Statement of Noncompliance
Due to the following listed violations, this project is not ready for occupancy:
C) 0 Supervising Professional Withdrawn From Project (Use A or B Bbove to indicate project status as of this date.)
0) 0 Project Abandoned }
3. SUPERViSING PROFESSIONALSIG..NAJ.I4RE..r.r;ij;þ .h1V' ~ rt¿.
0 Building 0 HVAC 0 Lighting- ~ é?~ J27t. Date ø
Name (Pleas~t or type) ~
Phone number / Customer ID # ?¿J~ Signature
(9c/O)r9?/~$J>¿) -----.
HVAC Permit Work Card
Job Address 465 N MAIN ST
Permit Number
116324 Create Date 09/16/2005
Owner
STAPEL PROPERTIES I LLC
Contractor GARTMAN MECHANICAL SERVICES
Category 510 -Ind. & Comm-Heating & Ventilating
Plan 02-75-0905
Fuel ~ c:æc:::J I I Electric I ~
System ~ew, 0 Replace
~ Forced Air I U Radiant I U Steam
U Electric I U Hot Water I U Suppl.
~ Value
D Other
I U AlC 1 ~ Vent
I U Con. Bumer I
$17,835.00
I
I
Chimney Type 0 Chimney A 0 Chimney B () Direct Vent . Not Applicable
Heat Loss . As Approved 0 Existing 0 Not Applicable I Value 0
. As Per Plan 0 Variable 0 Other I
BTU Rate Value
Use/Nature Church Ave - Install kitchen exhaust system as per plans. Hood to be run when any cooking
of Work equipment is in use.
Inspections:
Type Final
Inspector Allyn Dannhoff
approved w/cond.
Date 9/28/05
B & H FINAL OK WHEN NOTED CORRECTIONS ARE MADE. SEE FCN
DatelTime requested:
Notice Type:
Phone Number:
Access:
Ready DatelTime:
Requested By:
0 Reinspect Fee 0 Fee Waived
D Reinspect Fee Paid
- - - -- - - - - - -- - - - - - - - - -- - - -- -- - - - - - -- - - ------ - - - - - - - --- - - - - ------- --- -- - - - - - - - - - - - - - -- - - - - - - --
Date 10/20/05
Type Final
Inspector Allyn Dannhoff
apprOved
ONTRACTOR SENT IN VERIFICATiON THAT CORRECTIONS HAVE BEEN MADE
DatelTime requested:
Notice Type:
Phone Number:
Access:
Ready DatelTime:
Requested By:
0 Reinspect Fee 0 Fee Waived
D Reinspect Fee Paid
--------------------------------------------------------------------------------------------