HomeMy WebLinkAboutWPS-Generator-Wastewater Plant
*\\t-~
Page 1 of 5
Agreement No.
WISCONSIN PURI,IC SRRVTCR CORPORATION
ST A NDA RD AGRRF,MF,NT FOR TNTF,RCONNF,CTION
Agreement entered into this ~ 7d day of January, 2005, between CITY OF OSHKOSH,
with principal offices located at 215 Church Ave, Oshkosh WI 54903 (hereinafter the "Generator"), and
WISCONSIN PUBLIC SERVICE CORPORATION (hereinafter the "Company").
WITNESSETH:
WHEREAS, the Generator (intends to install) facilities for the purpose of generating electrical
energy ("Energy"), said generation facilities of 1760 KW (nameplate), declared as emergency back-up,
three phase, and synchronous type, as more particularly described on Exhibit A attached hereto (the
"Facility") to be located at OSHKOSH Wastewater Treatment Plant at 233 N Campbell Rd, Oshkosh WI.
WHEREAS, the Company, consistent with its policy of encouraging innovation and
conservation in the energy field, is agreeable to the Generator's installing said Facility.
WHEREAS, in accordance with regulation of the appropriate jurisdictional body, the Public
Service Commission of Wisconsin or the Michigan Public Service Commission (hereinafter the
"Commission of Jurisdiction"), the Company is charged with the responsibility of furnishing reliable and
cántinuous service to its customers at a fixed frequency and voltage within prescribed limits, and the
Company's electric utility system must be constructed and operated in a safe manner from the standpoint
of its employees, as well as the general public. The following are the principal concerns which must be
addressed in this Agreement by the Company and the Generator.
A. Potential electrical safety hazards resulting from the Facility energizing part of a distribution
system otherwise isolated by an outage.
B. Reliability and safety considerations relating to proper and adequate operation of protective
equipment associated with the Company's distribution system and the potential for the service entrance
equipment (e.g., fuses and circuit breakers) of individual customers being rendered inadequate by the
operation of the Facility.
C. The potential under various conditions for damage to customer-owned utilization equipment
because of irregularities in frequency and/or voltage resulting from operation of the Facility.
Page 5 of 5
Generator's expense, modify either the Equipment or WPSC's distribution system will be modified to
mitigate the problem. WPSC shall notify the Generator in the event any modification is needed and shall
obtain the Generator's agreement prior to commencing any WPSC modifications to the distribution
system for which the Generator is responsible for the costs.
15. In the event the Generator breaches this Agreement or otherwise fails to comply with any of
the terms or conditions set forth herein, WPSC shall have the right, in its sole discretion and in addition to
all other remedies at law or pursuant to this Agreement, to provide the Generator with required remedial
actions and a time1ine for corrective action to be taken. WPSC reserves the right to stop providing
electric distribution service to the Generator until such corrective actions have been implemented or in the
event that the Generator fails to implement corrective actions in the timeline prescribed by the Company.
16. Nothing contained herein shall restrict or otherwise limit the terms and conditions set forth
in the tariff filed by the Company with the commission of jurisdiction.
17. This Agreement shall remain in effect for as long as WPSC provides electric distribution
service to the Generator, unless sooner terminated by WPSC pursuant to Section 16 above.
C /7 Y of (Os/Irf'ð,S1I
~nerator. Ci1y. of Oshkosh) -
B~ Date: / -;27, ð¿S
Wð
City
1- ~7- trs-
re--n ~
l (Assistant City A:t2e~) k.
Date: ~
ISCONSIN P'1~ SE ICE CORPORATION
By: IL 'ù. Date: /Pt.r
¡¿~.
/~ ~ ~/(( /Qjj'
,.
-
.'
CITY HALL
215 Church Avenue
PO. Box 1130
Oshkosh, Wisconsin
54903-1130
City of Oshkosh
AA
(t)
OJHKOJH
May 25, 2004
Mr. Scott Hanson
Wisconsin Public Service Corporation
3300 N. Main Street
P.O. Box 420
Oshkosh WI 54903-0420
Re: Oshkosh Wastewater Treatment Plant Application for Interconnection of Small
Power Producers
Dear Mr. Hanson,
Enclosed is the requested WPS Interconnection Application for the Wastewater
Treatment Plant Generator Project.
I can be reached at (920) 232-5365 if you have any questions.
Sincerely,
~~:m. ~/
Ste~han M. Brand
Utilities Superintendent
Enclosures
CC: David Patek, Public Works Director
Shane Zenz, Strand Associates
0
"
Page of II
PUBLIC SERVICE CORPORATION
APPLICATION FOR INTERCONNEcnON OF
SMALL POWER PRODUCERS AND COGENERA TORS
5.000 KW CAPACITY OR LESS
This Application for Interconnection of Small Power Producers and Cogenerators is to be completed by the
project sponsor. For some smaller projects. data may not be available. however. please fill in all blanks
using N/ A when information is not applicable or not available because of project size:
Project Name
Oshkosh WWTP Standby Generators
Project Location
Oshkosh, Wisconsin
Generating Technology
Natural gas
Qualifying Facility Classification
NA
New or Used Equipment
New
Nameplate Rating
880 kW/1100 kva standby
KVA
Proposed In-Service Date
November 30, 2004
Proposed Agreement Ending Date
NA
Seller:
Name
City of Oshkosh
Address
215 Church Avenue P.O. 1130
StreetIP.O. Box
Oshkosh, WI 54903-1130
City. State. Zip Code
Seller's Representative for this project will be:
Name of Individual
Steve Brand
Position
Utilities Superintendent
Telephone
920-232-5365
Business Address
215 Church Avenue
-'.'-">'-'-""_."-~""
City/State
Oshkosh, WI
Zip 54903-11~~
3.
2.
2.2
2.2.
Page 2 of 11
I. GENERAL
Seller offers to provide energy and capacity in accordance with the terms and conditions of one
of the Standard Agreements (ask your local Public Service representative for copies).
.2
Seller understands that the Company will rely on the following representations in evaluating the
Project.
.3
Seller understands that this Project Proposal will be incorporated directly into and made part of
a Power Purchase Agreement and constitutes material terms of said Agreement.
ß. CHARACTERISTICS OF PROPOSED PROJECT
ESTIMATED OUTPUT
Peak Output @ 90°F. Ambient Temp. (KW)
880 KW
-,ow_»>o,,_....M,..w_w'>w>--->_W'>o-
Energy Output (MWH)*
On-Peak
Off. Peak
January
February
March
April
May
June
July
August
September
October
November
December
. Please list for all years if the energy output changes during the project tenn and attach a
statement of the reason why.
SITE INFORMATION
Prime Movers (For F.:ac"):
Both units identical.
Number
Cummins Model GTA 50 GS 3 Engine
Type
VEE Cylinder Natural Gas Engine
3.2
2.2.2
2.2.3
2.2.4
Characteristics
Governor Make
Capacity
Generator(s) (For Each):
Make
KWIK.VA
Speed
Cycles
Amps
Power Factor
Winding Connection
(Wye or Delta)
Exciters (For Each):
Volfe
Type
Voltage Regulator Make
Name Plate Information
Page 3 of I J
Isochronous
Cummins Onan Powercommand
~8..Q~- kW/l10_~=Jcva standby
Both units identical.
_.Ç~ins_~;ti~r Model GFLC
---~QJcW¿.1:.1:92- _kva standby
18 0 O_~-------
60 Hz
152 amps
...----.. .~._-----.
0.8
-~-,--^"----,.,,_.,~._---,_.-
Wye
4160 V
"----'----".
Electronic
Cummins Onan powercommand
Power Transformers for Station Supply (For F.:ach): NA
Size
Type
Name Plate Information
-~...~_.-
...--.-----.
3.3
Page 4 of II
Liahtnina Arrestors (For f:ach)'
Voltage
Type
Make
Arrangement (Identify on
line diagram)
Service Panel or Substation Equipment (As Applicable):
a) Substation Transformers (For Each):
NA
Name Plate Data
Connections
(Wye or Delta)
b) High Voltage Switchgear:
NA
Make
Type
Continuous Current
Rating
Interrupting Rating
c) Low Voltage Switchgear:
(Medium)
Make
Shallbetter
Type
Metal clad
Continuous Current
Rating
1200 A
Interrupting Rating
250 mva
d) Station Ground:
Describe
Ground mat
3.4
3
3,
3. .2
Page 5 of
IlL D~TAn.¡:D PROPOSAL DATA
PROJECT OWNERSHIP AND FINANCING
Project Ownership
a.
What is the sponsoring firm's legaJ structure (e.g.. corporation, partnership, wholly-owned
corporate subsidiary, etc)? municipality
b.
If the sponsor is a publicly-held company, have the required SEC minas been attached
(yes. no, or not applicable)? NA
c
If ownership is a partnership, please name all equity partners
NA
...-..---..
d.
If the sponsor is a wholly-owned subsidiary, will debts and liabilities of the sponsor be
secured by assets of the parent firm? NA
Yes
No
Financing
NA
a.
An audited income statement and balance sheet for the sponsors and a statement by a
Certifaed Public Accountant that the sponsor has sufficient capability to fully finance the
project has been attached?
Yes
No
b.
A statement from a reputable financial institution expressing the opinion that the project
as described is able to receive financing has been attached?
Yes
No
c.
What percentage of the required project capital included in the financing plan does the
sponsor currently have commibnents for? Please attach financing plan and documentation
of capital commibnents.
11/0
d
What is the sponsor's planned equity in the project expressed as a percentage of total
capitalization?
%
e.
If the facility is a cogenerator. to what degree is the sponsor's ability to finance the project
dependent on steam sales?
f.
What restrictions on debt financing or tax indemnification exist?
g.
Optional: What is the project's annual debt coverage over the debt term?
3.5
Page 6 of 11
3.2
PROJECT TECHNICAL AND ENVIRONMENTAL FEASIBILITY
NA
Attach a complete description/conceptual design of the proposed project describing the proposed
project technology. including associated emissions control, cooling and make-up water
requirements and availability, fuel supply plan, and a plan for use or disposal of by-product waste
materials.
33
PROJECT SITE SELECTION
Has the Seller identified a suitable site for the project?
@)
Does the Seller own. have a lease. or have an option for the site? (If yes. please attach evidence
of control.)
No
C9
No
3.4
PROJECT SCHEDULE
Seller's Proposal is based on the following schedule of major project milestones
Start
a. Obtain Critical Construction
Pennits & Licenses
b. Obtain Construction Financing
c Award Major Equipment
Purchase Agreements
d. Site Construction/Installation March 2004
c. Major Equipment
Fabrication & Delivery June 2004
f. Startup Testing & Place in
Commercial Operation October 2004
Complete
October 2004
September 2004
November 2004
3.6
].5
].5
3.5.2
PERMIT STAIDS NA
Federal Permit (application and approval) status is as follows
fmni1
FERC Certification
FAA
EPA Air Pollution
Control
Corps of Engineers
._0".-
Plan for Application
Submittal Complete
Application
Submitted
Approval
Received
State and Local Permits (application and approval) status is as follows:
Commission CPCN
DNR Construction
Run Off
DNR WPDES
DNR Air Quality
l.ocal Zoning
Local Building
Local Building Permit
-
Plan for Application
Submittal Complete
1.7
Application
Subm itted
March 2004
Approval
Received
NA
Page 7 of
Not
Applicable
Not
Applicable
"
3.6
3.1
3.8
Page 8 of
Agreement
Description
Issued
For Bids
Agreement
Awarded
Bids
Received
Not Developed
INTERCONNECTION
The electrical intercoMection will likely be a radial 24.9 KV line. What is the date by which the
24.9 KV source would have to be available at the site (perhaps for construction power)?
Is the reliability with a radial 24.9 KV line interconnection acceptable?
@
No.
PROJECT LONGEVITY
Has a complete plan for management and operation of the facility been developed?
9
No.
Please describe the plan for management and operation:
maintenance and testinq
Re~u~ar preventive
RELIABILITY
NA
What is the predicted annual number of hours that the facility will be available to deliver energy
to Public Service?
Hrs
Please list for all years if the availability changes during the project term and attach a
statement of the reason why.
3.8
3.8.4
Page 9 of II
Scheduled Maintenance
Scheduled Maintenance Time
<.»_.~-~".,",~>._,,<_HrsIY r
Frequency of Scheduled Maintenance
TimesIY r
_.'<-,""-
Months of Year Scheduled Maintenance Performed
Public Service Notification of Scheduled Maintenance-
Weeks in Advance
Weeks
Staffing Levels for Maintenance & Operation
,,~"~-~--»,,_.,,--
Unscheduled Maintenance
Full Forced Outage Time
HrslYr
Partial Forced Outage Time
HrsIY r
Percent Derate Under Partial Forced Outage
%
Public Service Notification of Pending Forced Outage
Hrs
Identify any other times the facility may be unavailable for generation:
Describe any special features or facilities incorporated into the design to assure reliability:
U)
Controls allow connection for seconds maximum
I jt1-10-5 t6[f5 e.'-J ~ lltj-\l;~
3.9
Page 10 of
DISPATCHABILITV NA
Check the most applicable item
MUST RUN. The Project is must run. The Facility will generate at full capacity
24 hours per day. all year. except during scheduled or forced outages.
CURTAILMENT OF MUST RUN FACILITY. The Project is must run from
_a.m. Monday (or Tuesday if Monday is a holiday) through - p.m. Friday
(or Thursday if Friday is a holiday) and the Company at its option may take all or
a portion of the Project off-line during all other hours.
FULLY DISPATCHABLE. The Project is fully dispatchable.
If fully dispatchable. please answer the following'
a)
What control will Public Service have to dispatch the unit?
~,,_.~.~
~._-->~_.
b)
What equipment will be available for Public Service dispatch?
c)
Response time for dispatch:
ALTERNATE FACILITY DISPATCH PLAN. Describe:
FUEL TYPE &: EFFICIENCY
3.10.
Check applicable item
NA
Project will have a PURPA efficiency greater than:
_60%
.SO%
40%
Project will use renewable resources
Project is a dual fuel facility that will use coal and oil or gas
Project will use coal only
Project will use gas or oil only
Other - please explain:
3.10
. .
.
Page
of
VOLTAGE CONTROL NA
Describe the type and accuracy of voltage control
IV. CERTIFICATION
Seller hereby certifies that all of the statements and representations made in this Project Proposal, including
the Proposal Data and attachments, are true to the best of Seller's knowledge and belief, and agrees to be
bound by the representations, tenns, and conditions contained in the Guidelines For Power Purchases From
Qualifying Facilities and the Standard Agreement.
Submitted by
Shane Zenz
Print Name of Officer:
-¥.Y.Of ~..ShkOSh
. .",,(U),fl~
Steve Brand
Seller:
Signature of an Officer of Seller.
6-- l3,-oli
Date Signed
3,
,
Oshkosh WTP
PowerCommand Digital Paralleling
Medium Voltage Applications - Utility Parallel
A ,,1-
Sequence of Operations
Revision: A Date 4/2/04
Oshkosh WTP Close Transition Transfer Pair Sequence of Operations
Loss of Normal Power: The system is given a utility failure signal from the
utility protective relay device. After a time delay (adjustable from the
touchscreen), all generator sets automatically and independently start,
accelerate to rated frequency, and build up to rated voltage. The "First Start"
system monitors this process, and on finding a generator set at 90% of rated
voltage and frequency, automatically disables the other units from closing to the
bus, and closes the first ready unit to the bus. At this time the utility main
breaker is opened, non-essential loads are shed, and the generator main breaker
closes connecting the generator set to the system bus.
The priority (Load Add) controls prevent overloading of the system bus by
providing inhibit signals to prevent operation of selected loads on the system
until sufficient generating capacity is available on the bus, or until the
priority override switch 'on the touchscreen control is actuated. There are four
double-ended unit substations (USS #1,2,3,and 4)and two influent pump feeders in
the system that shall be shed and added in the following priority (highest to
lowest): Priority 1 - USS #1 (This load shall not be shed except in an
emergency); Priority 2 - Raw Sewage Pumps, IV,lC,2V,2C; Priority 3 - USS #2 Right
end/USS 3 Right end; Priority 4 - USS #2 Left end/USS 3 Left end; Priority 5 -
USS #4 Left end; and Priority 6 - USS #4 Right end.
Note the following statements for the operation of
features:
~Load Add" and ~Load Shed"
Load Add Feature: The load add feature will have one (1) level for each generator set. Each
additional load will be added after a preset time delay. Each feeder breaker will have a dedicated
relay. The highest load add level is "1" so that it will be added first. Relays are user programmable
from the touchscreen to allow each relay to be individually assigned to any load add level available.
The system will have seven load add levels. It is pennissible to assign multiple relays to an
individual load add level. This pennits re-assigning load add levels to all transfer switches or circuit
breakers connected to the relay without re-wiring. «5
Load Shed Feature: The load shed featur '11 have one (1) level established for each generator
set (levels O,I,2,...,etc./relays 1,2,3,...,etc . Each additional load will be shed after a preset time
delay. The highest load shed level is " so that it will be shed first. The lowest load shed level is
"0" and it will never be shed. Relays are user programmable :&om the touchscreen to allow each
relay to be individually assigned to any load shed level. The system will have seven load shed
levels. It is permissible to assign multiple relays to an individua1load shed level. This pennits re-
assigning load shed levels to all transfer switches or circuit breakers connected to the relay without
re- wlnng.
After the first unit is('clos~d to the bus, the control of the remaining units i~'
switched to the synchronizer in each generator paralleling control, which causes
the generator set to synchronize.with the system bus, and then close to it at the
proper time.
.
.
As each unit closes to the bus, the unit assumes its proportional share of the
total load on the bus.
If a generator set fails to start, after the overcrank time delay the unit will
be shut down, and an alarm will sound. If a unit fails to synchronize, after a
preset time delay an alarm will sound, but the unit will continue to attempt to
synchronize until signaled to stop by manual operation of the control switches on
the generator set.
1
Cummins anan
Apríl28.2004
,¡,
Oshkosh WTP
PowerCommand Digital Paralleling
Medium Voltage Applications - Utility Parallel
Sequence of Operations
Revision: A Date 4/2/04
In the event that one generator set fails when the system is supplying emergency
power, the failed generator set will be taken off line by opening the pertinent
generator breaker.
With one or more generator sets off line, the priority control will prevent the
lowest priority loads from being added to the system without manual intervention.
The priority override controls on the touchscreen may be used by an operator to
manually add low priority loads to the bus, if he determines that generator set
capacity is available to serve the loads. Bus overload monitoring shall protect
the first priority loads in the event that the bus is inadvertently overloaded
due to operator error.
If a bus overload occurs for any reason, a load shed signal will be generated to
initiate load shedding in the system. If the bus does not return to proper
frequency within a predetermined period of time, additional load shed signals
will be generated.
Load Demand Mode: When the system is running in the emergency mode with the ~load
demandw switch on the touchscreen in the ~onW position, controls shall
continuously monitor the total load on the bus. If the total load on the bus
falls below preset limits for a period of 15 minutes [time delay is adjustable
from the touchscreen], the controller will automatically shut down generator sets
in an operator predetermined order, until the minimum number of generator sets
required to operate the load remain on the bus. The purpose of this function is
to allow the generator sets to operate closer to rated capacity decreasing fuel
consumption and reducing component wear on the system.
On sensing that the available bus capacity is being approached, the standby unit
will automatically be restarted (in the reverse order of which they were shut
down) and paralleled with the bus to assume its proportional share of system
load.
Return of Utility Power: When the utility power supply has recovered to proper
voltage conditions and all system start signals are removed, the system enables a
time delay [time delay is adjustable from the touchscreen] before initiating the
retransfer sequence. On the completion of the retransfer time delay [time delay
can be bypassed from the touchscreen], the system will begin a retransfer process
in either open or closed transition mode, as selected by the operator. If running
in the closed transition mode, the system shall synchronize the generator bus to
the utility, close 52-UM, ramp down load on the gensets to a minimum value, then
open 52-GM. The generator set paralleling breakers will open and the generator
sets will then run unloaded for a cooldown period and shut down.
If the operator has selected open transition mode, 52-GM will open and 52-UM will
close. The generator set paralleling breakers will open and the generator sets
will then run unloaded for a cooldown period and shut down.
If a system start signal is received during the cooldown period, one generator
set shall immediately close to the emergency bus and all other units sha¡l
synchronize to it, as described in ~Utility Power Failurew above.
Test Mode (open transition): Operation of the test switch will simulate a power
failure in the system, causing the genset to start, and the system to transfer as
described in "Loss of Normal Power" above. Returning the test switch to normal
will cause the system to return to normal power as described in "Return of Normal
Power (open transition)" above.
Test Mode (closed transition): Operation of the test switch will simulate a power
failure in the system, causing the genset to start, and the system to transfer as
described in "Loss of Normal Power" above. Returning the test switch to normal
will cause the system to return to normal power as described in "Return of Normal
Power". Once all generator sets are on the emergency bus (52-Gs are closed), the
system will synchronize across and close breaker 52-GM. The bus will then ramp up
to assume the load. When the load supplied by the utility reaches a minimum level
52-UM is opened.
"- ,.'
2
Cummins Onan
April 28, 2004
t-'
Oshkosh WTP
PowerCommand Digital Paralleling
Medium Voltage Applications - Utility Parallel
Sequence of Operations
Revision: A Date 4/2/04
, ..
When the system is running in the test mode with load demand enabled, controls
shall continuously monitor the total load on the bus. If the total load on the
bus falls below preset limits for a period of 15 minutes [time delay is
adjustable from the touchscreen], the controller will automatically shut down one
generator set. On sensing that the available bus capacity is being approached,
the standby unit will automatically be restarted and paralleled with the bus to
assume its proportional share of system load.
Returning the test switch to "Normal" position will cause the system to return to
normal power as described in "Return of Normal Power (closed transition)" above.
Test Mode (Without Load): The operator from the touchscreen can put the system
into a test without load mode. In this mode of operation the generator sets
shall start, build up to rated speed and voltage, synchronize and close to the
generator bus, but system loads shall not automatically transfer to the generator
system.
Automatic Operation - Peak Shave Mode: Durinq the peak shave mode. Load Demand
mode will be disabled.
The peak shave mode may be selected via dry contact or locally from the Operator
Interface Touchscreen. On receipt of this signal, the gensets start and the
system connects to the bus as described in "Loss of Normal Power" above.
Tr king MOde Se ected: Once all generator sets are on the emergency bus (52-Gs
are losed), t system will synchronize across and close breaker 52-GM. The
Mast Control PLC will calculate the required generator KW level using a
trans ucer in ut from the switchgear. The bus will then ramp up to assume the
load a ove t e peak shave KW setting (set on the operator touchscreen). This
will aI ow e Utility to maintain a constant load while the generator system
adjusts to upply the load -peaks".
ode Selected: Once all generator sets are on the emergency bus (52-Gs
), the system will synchronize across and close breaker 52-G. The bus
amp up to assume the load up to the base load setting on each
et(set on the generator set setup screen). If the building load is
is setting, excess power will be exported to the utility. The 32
he SEL relay is disabled in this mode.
On re eipt 0 a peak shave shutdown signal, the generator bus will gradually ramp
down 0 a pr set level, and 52-G will open. The generator set paralleling
bre ers wil open and the generator sets will then run unloaded for a cooldown
per'od and sh t down.
I there is a power failure while in the Peak Shave Mode, utility protective
r lay will trip 52-liM.
Tie Breaker: The tie breaker in the distribution gear is normally closed. The
tie breakers in USS 1,2,3,and 4 are normally open manually operated. The.
distribution gear tie will remain closed unless the operator opens it to maintain
one side or the other. The normal operation is to feed each half of USS
1,2,3,and 4 from the distribution gear with the ties in the substations open. If
operator opens the tie in the distribution gear for maintenance, they have manual
procedures for closing the ties in the substations, opening the tie in the
distribution gear, and feeding both halves of the substations from either the
utility source or the generator source.
3
Cummins anan
April 28, 2004
--------
-, --,-- - ._-
u
J,
~
'"
~~
~
ï
-
¡¡
~
I
s
~~
~'-~I:~l
- ~
'-rH H
. ~ ...-"
~~
r -- -- n n - _h- - -- - - - - ----- ----~'~'~::o2i~~_~_--- ----,
¡ . :
, '
, '
,
,
,
,
,
,
,
,
,
,
,
1
1
1
,
,
,
,
,
5:
~:
8'
",'
¡:!'
~[
~:
.,'
ä:
,
,
,
,
,
1
1
1
1
,
,
,
,
I
I
,
I
I
I
,
,
I
L - --- - - - - n - -- - - - -- - - --- -- - -- - -- - - - - -- --- - n_____J
L___n - -- --- __n--___-___n ------ _-__n
~~'6D ~
~~ '
~~ ~~ ~
~! -..----- -_oj :
,
I
i
~¡['È ~ YT;T;l :
" -" . liUü "
~
'1
~
-jH
8~
>~
ä
i
i
,,; "
~I
~i
<" .
~~g %~
~~§ >--r---<~ .:...
o"';r. ,
.$ Ji.,.2 ;
T'~
L .-..-"- - ,- - _.._.
Q
0
u
l'
---
('
(,
-
~~
t'g
""
~ -"
~Š~~
~ ~~'->
"-"
'"
-<
A~~
"'"
~ z¡';'
~ '" ~
w ¡:
ð. ~ ex)
-0 ~;: z ....
~ ~!! 8 ~
<>-!T '" I
!¡)' i=:' 0
" z '"
;]I ï <0-
U ;i?t
'"
'. ~
I¡ C1
-<
u-
C1
I: ~
'-'
§.
.. ~
~'!3 ';~
~i!i~
000.,<3
æ r,:
""'<':<.'o>!>
""",ÚH
:gê:;::S>!>
.;¡;;g~ t ""
-, 't<!i!!;!!; g¡ i
-;:1g;~!¡g; ,
,'-
""'I
~ ~
m
~
",
.
:: :: : ¡
:: :: :
- I-
(\
\'i
A~i
I h /0 >
Oshkosh Wastewater Treatment 4.16kV Main Service Protection
Overcurrent protection settings
These are non-directional overcurrent elements set for normal operation with generation
offline. These initial settings are made to coordinate with a S&C. universal, 200K speed
fuse. The actual fuse size will need to be verified with WPS and time dial setting may
need some tweaking.
5lPP = 1.75
5lPC = U4
5lPTD = 5.00
5lPRS =N
CT Ratio = 1200/5
5lGP = 1.25
5lGC = U4
51GTD = 5.00
51GRS =N
Svnch-check relay
The following settings are recommended for the synch-check relay:
25VLO = 105 volts
25VHI = 130 volts
25SF = 0.10 Hz
25ANGI = 5.00 deg
25ANG2 = 10.00 deg
LL-LB, LL-DB only
Overvo I tage/undervo I tage
Over voltage protection is set to protect plant equipment from overvoltage conditions due
to runaway tap changers or unloading the utility to quickly with generation. Undervoltage
will be set to allow utility to complete auto-reclosing sequences. The following are
recommended settings:
59PIP = 132 volts
Delay = 30 cycles
27PIP = 108 volts
Delay = 3600 cycles
Frequency Relay
The following are recommended settings:
81U = 59.3 Hz
Delay = 6 cycles
810 = 61 Hz
Delay = 10 cycles
F,XHTRTT R
PG 1 Tariff
WISCONSIN PUBLIC SERVICE CORPORATION
P.S.C.W. Volume No.7
Original
Sheet No. E4.00
Sheet No.
Schedule PG-1
Replaces
Amendment 556
Parallel Generation - No Purchase by WPSC
Electric
EFFECTIVE IN
All territory served.
AVAILABILITY
To customers contracting for electric service, generating
electrical energy, and not desiring to sell any electrical energy
to the Company.
MONTHLY RATE
Deliveries from the Company to the customer shall be billed in
accordance with the standard applicable rate schedules of the
Company.
Flow of energy from the Customer's generation facilities into the
electrical system of the Company shall be supplied by the Customer
without charge to the Company.
SPECIAL RULES
1.
The Company shall install appropriate devices on the Company's
metering facilities to prevent the meter from recording any
flow of energy from the customer's generation facilities into
the electrical system of the Company.
PARALLEL GENERATION RULES
See Schedule PGX, starting on Sheet No. E4.30.
Issued 5-21-81 Effective for Service Rendered
On and After 5-21-81
PSCW Authorization By Letter Dated 5-20-81 (TBN)
EXHIBIT C
PGX Parallel Generation Rules
WISCONSIN PUBLIC SERVICE CORPORATION
P.S.C.W. Volume No.7
2nd Rev.
Replaces 1st Rev.
Amendment 570
Sheet No. E4.30
Sheet No. E4.30
Schedule PGX
Parallel Generation - Rules
Electric
PARALLEL GENERATION RULES
The following rules shall apply to all customer owned generation facilities that
are interconnected with the company's power supply:
1.
Interconnection of a generating facility with the company shall not be
permitted until application has been made to and approval received from the
company. The company may withhold approval for good reason such as failure
to comply with applicable utility or governmental rules or laws. The
company shall require a contract specifying reasonable technical connection
and operating aspects for the parallel generating facility.
2.
The company may require that for each generating facility there be provided
between the generator or generators and the company system a lockable
load-break disconnect switch. For installations interconnected at greater
than 600 volts a fused cutout switch may be substituted, where practicable.
The switches shall be accessible to the company for the purpose of
isolating the parallel generating facility from the company system when
necessary.
3.
The company shall require a separate distribution transformer for a
customer having a generating facility where necessary, for reasons of
public or employee safety or where the potential exists for the generating
facility causing problems with the service of other customers. Ordinarily
this requirement should not be necessary for ctn induction-type generator
with a capacity of 5 Kw or less, or other generating units of 10 Kw or less
that utilize line-commutated inverters.
4.
Where necessary, to avoid the potential for a facility causing problems
with the service of other customers, the company shall limit the capacity
and operating characteristics of single-phase generators in a manner
consistent with its existing limitations for single-phase motors.
Ordinarily single-phase generators should be limited to a capacity of 10 Kw
or less.
Continued to Sheet No. E4.31.
Issued 9-8-83 Effective for Service Rendered
On and After 10-1-83
PSCW Authorization By Letter Dated 8-24-83 (TBN)
e
OJHKOfR
ON THE WATER
Memorandum
To: David Patek, Public Works Director ¡J
From: Stephan M. Brand, Utilities Superintendent Jir¡h.- ¡n,ßJLlL~
Date: 2/15/05
Re:
WWTP Generator Project 03-04 Operating Agreement with WPS
Attached is a copy of the executed agreement with Wisconsin Public Service to allow
for parallel generation during the use of the emergency generators at the wastewater
treatment plant. The agreements will be distributed as follows: Original- City Clerk,
Copy City Attorney, Copy Public Works, Copy Wastewater Treatment Plant. Please let
me know if you have any questions.
--
Wisconsin Public Service Corporation
(a subsidiary of WPS Resources Corporation)
700 North Adams Street
P.O, Box 19001
Green Bay, WI 54307-9001
1/31/2005
Mr. Steven Brand
c/o City Hall
215 Church Ave.
Oshkosh, VVI,54903
Re: WPSC Parallel Generation Application/Contract for WPS account 668047
Dear Mr. Brand:
Please find the enclosed copy of the WPSC parallel generation contract for your records. Your system is
approved and in compliance with the rules and rate specified in the contract. Thank you and feel free to
call if you have any questions.
sr¡y, tt ¡L .
Ken Kozak PE
WPSC
700 N. Adams Street
Green Bay, WI 54307
920 433 2934