HomeMy WebLinkAbout2005-Electric
e
OSHKOSH
ON THE WATER
CITY OF OSHKOSH
No
114598
ELECTRIC PERMIT - APPLICATION AND RECORD
Job Address
0 Change
0 Temp
Owner MILLS PROPERTIES INC Create Date 06/10/2005
Category 643 - Commercial-Addition/Remodels Plan
10 Overhead
. N/A Type 0 Underground
Circuits 0 Fixtures 0
Switches 0 Receptacles 0
177 N WASHBURN ST
Contractor
SUBURBAN ELECTRICAL ENGINEERINC
Service
10 New
Volts
Amps
0
Appliances
Use/Nature of Poer and lighting for new entrance
Work
Fees: Valuation
$50,000.00
Plan Approval
$0.00
Permit Fee Paid
$334.00
Issued By:
Date 06/10/2005
U Permit Voided I
Parcelld # 0614000000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
Agent/Owner
Address
709 HICKORY FARM LN
APPLETON
WI 54914 - 0
Telephone Number
920-739-51 56
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Electric Permit Work Card
Job Address 177 N WASHBURN ST Permit Number 114598 Create Date 06/10/2005
Owner MILLS PROPERTIES INC
Contractor SUBURBAN ELECTRICAL ENGINEERIN(
Category 643 - Commercial-Addition/Remodels
0 ChangeO Temp. N/A I Type 0 Overhead
Circuits 0
0 Underground . N/A
Fixtures 0
Receptacles
Value $50,000.00
Service b New
Volts
Amps
~
Switches
Fee
$334.00 0
Appliances
Use/Nature
ofWork
Poer and lighting for new entrance
Inspections:
Date 07/13/2005
Type Underground
Inspector Kevin Benner
approved w/cond.
Request Line - do you want to see the UG done so far for the gate hut? otherwise Neil will take pictures.
All was backfilled. but i did notice a warning tape installed approximately 18" BFG
DatelTime requested: 07/12/2005 08:28 AM
Access:
Notice Type:
Phone Number: 841-7073
Ready DatelTime: 07/12/200508:28 AM Requested by:
--------
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
SUBURBAN ELECTRICAL ENGINEERING
Date 07/21/2005
Type Underground
Inspector Kevin Benner
no time
Pouring concrete and installing traffic loops in the concrete
DatelTime requested: 07/20/2005 08:3§_~ Notice Type:
Access:
Phone Number: Neil841-7073
Ready DatelTime:
~21/2005 07:30 AM
Requested by:
0 Reinspect Fee 0 Fee Wavied
0 Reinspect Fee Paid
Electric Permit Work Card
Job Address 177 N WASHBURN ST
Permit Number 114598 Create Date 06/10/2005
Owner MILLS PROPERTIES INC
Contractor SUBURBAN ELECTRICAL ENGINEERIN(
Category 643 - Commercial-Addition/Remodels
Circuits
I Type 0 Overhead
0
Q Underground. N/A
Service b New
Volts
0 ChangeO Temp. N/A
Fixtures
Amps
0
Switches 0
Fee
$334.00 0
Receptacles
Value
$50,000.00
Appliances
UseJNature
of Work
Poer and lighting for new entrance
Inspections:
Type Consultation -- Inspector Kevin Benner
approved w/cond.
Date 08109/2005
Evaluate working space for the service location before the equipment is installed
Need to relocate the panel or change the constuction of the bollard base to create the required working space.
DatelTime requested: 08/09/2005- 09:42 AM Notice Type:
Access:
Phone Number: 841-7073 Neil
Ready DatelTime: 08/09/2005 09:42 AM Requested by:
--
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Type Final
Inspector Kevin Benner
not approved
Date 11/03/2005
Request Line - yard entrance - for next week, advise Neil when you can schedule
Electrical panel is bonded, ii9ht poles not 9rounded, J-Boxes require grounding where the ground wires are
terminated
DatelTime requested: 10/26/2005 01 :26 PM
Access:
Wants to be present.
Notice Type:
Phone Number: 841-7073
~----
Ready DatelTime: 10/31/200507:00 AM Requested by:
---
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
SUBURBAN ELECTRICAL ENGINEERING
----- ----
Electric Permit Work Card
Job Address 177 N WASHBURN ST
Owner MILLS PROPERTIES INC
Permit Number 114598 CreateDate 06/10/2005
Contractor SUBURBAN ELECTRICAL ENGINEERiN(
Category 643 - Commercial-Addition/Remodels
Circuits
I Type 0 Overhead
0
0 Underground. N/A
Service b New
Volts
0 ChangeO Temp. N/A
Fixtures
0
Amps
~
Switches ~
Receptacles 0
$50,000.00
Fee
$334.00 0
Value
Appliances
l
Use/Nature
of Work
Poer and lighting for new entrance
Inspections:
Date 12/28/2005
Type Re Final
Inspector Kevin Benner
no time
Neil from Suburban stated that the violations have been corrected.
DatelTime requested: 12/2812005 08:06 AM
Access:
Notice Type:
Phone Number:
Ready DatelTime: 12/28/200508:06 AM Requested by:
--
0 Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid