ELECTRIC PERMIT - APPLICATION AND RECORD
Owner MERCY MEDICAL CENTER OSH INC
Category 643- Commercial-Addition/Remodels
Type I~ Overhead
Circuits 0
Switches 0
No 99552
Create Date 01/22/2003
Plan
~ Underground
Fixtures
Receptacles
Appliances
Use/Nature of COMM/LATE PERMIT/Misc jobs done the past 1 1/2 years (T & M work conduced in 2001 & 2002).
Work
Fees: Valuation
Issued By:
$252,000.00 Plan Approval $0.00 Permit Fee Paid
$996.00
Date 01/22/2003
Permit Voided
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
Signature
Date
Agent/Owner
Address 1775 E SHADY LN NEENAH WI 54956 - 0 Telephone Number
(920) 720-5200
ELECTRIC
A DIVISION OF MICHELS CORPORATION
1775 E. Shady Lane
Neenah, WI 54956
Mailing: P.O. Box 7199
Appleton, WI 54912
(920) 720-5200
Fax: (920) 720-5214
E"LECTRICAL
CONTRACTORS
January 20, 2003
City of Oshkosh
P. O. Box 1130
Oshkosh, WI 54903-1130
Attn: Kevin Benner
Electrical Inspector
Re: Mercy Medical Center
Code Corrections
Gentlemen:
Enclosed is the Correction Notice for the items that were addressed at
Mercy Medical Center and is signed by our employee Brian Oehlke.
Also enclosed is a $996.00 check for work performed without permits in
the past which total $282,000.00
I will itemize jobs performed:
A. Mercy MiscellaneOUs Jobs (Our Job #17006)
1. Elevator by-pass switch
2. ER Vending Machines
3. Pediatrics automatic doors
4. Emergency feed to elevator (100 Amp)
5. Volunteer door holder
6. Replace sealtight on deep fryer
7. Emergency power in Sleep Lab
8. Change switch in Dictation Room - ER
9. intercom buttons in BehaVioral Health
10. Install lights sub acute
11. Outlets in Cath Lab #1
12. Light by volunteer board
13. Pay phone area lights
14. LVP room light switch
15. Panic button Room lh585
16. Change 2 X 2 light to can light
17. Install camera cable in Gift Shop
18. install keypad switch
19. Add circuit in office
20. install antenna in Security
21. install door holder Room WH125
Commercial / Industrial / Residential Wiring & Maintenance · Tele-Data Network Cabling / Fiber Optic Installation & Repair
Transmission / Distribution / Sub-station Construction & Maintenance · Sound / CCTV / Security / Fire Alarms
22. Install 2 - 2 X 4 trofffers in X-ray
23. Install magnetic door holders ICU
24. Repair clock wiring
25. Change 6 fixtures Dr. Buck office
Total $48,607.00
B. Miscellaneous Work (Our Job #17316)
Total $ 2,577.00
C. Miscellaneous Work (Our Job #27104)
1. Stairwell receptacles
2. Lighting display case
3. Install clock system (receiving)
4. Install nurse call (Breast Lab)
5. Change can lights (Sleep Lab)
6. Install control wiring (med. Gas)
7. Install fire door release
8. Install heat lamp fixture (Patient Room)
9. Install circuit (Ultrasound)
10. Remove elec. whip (Pharmacy)
11. Install hardware for nurse call
12. Install call lights (Ortho Suite)
13. Move pump controls (Dialysis)
14. Install 7 receptacles coax (ER)
15. Install speakers (Kitchen Cafeteria)
16. Install normal duplex receptacle
17. Install light pole base (Oakwood)
18. Install emergency power (2nd Floor Rehab)
19. Install 3 receptacles (small lab)
20. Install emergency circuit for water heater
21. Update as-built drawings
22. Install lighted key switch (Loading Dock)
23. Install 120 volt circuit (fire)
24. Install receptacle in Locker Room
Total
$32,349.00
D. Mercy Miscellaneous Jobs (Our Job #17066)
1. Hydro Therapy Door Holder
2. Install under cabinet light
3. Install under cabinet light (GF135)
4. Locate U. G. conduit for signs
5. Install wiring for window shades
6. Install 4 can lights in soffet
Total
$13,331.00
E. Cath Lab (Our Job #17077)
F. Linear Accelerator (Our Job #17179)
G. Dietary Office (Our Job #17267)
H. E R Miscellaneous (Our Job #17306)
I. Breast Lab Miscellaneous (Our Job #17337)
J. CT #1 - HVAC (Our Job #27166)
K. Misc. Mercy Expansion (Our Job #27173)
L, Dr. Jansen Suite (Our Job #27182)
M. Mercy Miscellaneous (Our Job #27183)
1. Cancer Center Automatic Door
2. ENT Suite Remodel
3. Install receptacle Suite 220
4. Install VAV box entrance
5. Neuro Suite (Oakwood)
6. Install one plugrnold receptacle
7. Install light Scott Man. Office
If you have any questions or comments please advise.
Sincerely,
SUPERIOR ELECTRIC
Don Verhagen
Superintendent
Total $35,614.00
Total $76,338.00
Total $ 572.00
Total $ 1,397.00
Total $ 591.00
Total $48,203.00
Total $ 7,649.00
Total $ 7,061.00
Total $ 7,672.00
Oct, 28 02 03:45p Oshkosh Inspections 920-236-5084
p.3
City of Oshkosh
Division of Inspection Services
P.O. Box 1130
Oshkosh, WI 54903-1130
Phone (920) 236-5050
Fax (920) 236-5084
O./'HKO./'H
ON THF WATER
ELECTRICAL PERMIT APPLICATION
All information after bold categories must be provided.
Incomplete applications will not be processed.
· Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) will result m fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
If you are a contractor participating in the Permit Fee Account System and have adequate funds, check here
if you want this processed through your account []
JOB ADDRESS ..
OWNER
CONTRACTOR
DATE
CHECK ~I ALL APPLICABLE
USE CATEGORY
nSingle Family nDuplex C1Multi-Family nRental
SERVICE DNew F1Tempomry TYPE
nChange I~Not Applicable
[~Commercial nlndustrial
nOverhead ~[Not Applicable
[=]Underground
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
Volts / Receptacles #
Phase
Amps' , Switches #
Circuits #
Fixtures #
CHECK i~I ALL APPLICABLE
F1Range nDishwasher nGarbage Disposal VIDryer
nFan OR Blower DFumace V1A/C nElectric Sign
nMotors nGas Pumps [] Other
DESCRIPTION OF ALL WORK BEING DONE
nWater Heater
OD
VALUE (Including labor and all materials including light fixtures) $ &~t 600, "-
3/02
OSHKOSH
ON THE WATER
RECEIVED
NOV 2 6 00Z
·" INSPECTION SERVICES DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
Room 205
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
SUPERIOR ELECTRIC
Issue Date 11/25/02 Compliance Date 12/25/02 IMMEDIATELY Compliance No
Address 500 S OAKWOOD RD Inspected By Kevin Benner 236-5046
Name
[~ Owner I MERCY MEDICAL CENTER OSH INC
?_J Contractor I SUPERIOR ELECTR C COMPANY
L-J Other
~J Inspector
Sent to
Address City State Zip Code
PO BOX 3370 OSHKOSH WI 54903 -3370
1775 E SHADY LN
NEENAH WI 54956 -0000
0 -0000
~ Required for Occupancy t Occupancy Commercial Notice ~ First ~t Final O Other I
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
an dior occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 12/25/02
Introduction IOn June 21,2000 a final inspection was conducted for Mercy Medical Center. The final inspection was not approved but the
ospital was occupied. I reviewed the outstanding violations with Kris Lamers from Superior Electric. I understoood that he
ad several outstanding issues to address for the owner which is normal for a project of this size. Fie assured me that the
iviolations would be corrected. It is m ¥ understanding that the foilowing violations have not been addressed.
item# 1 Code MOll-32 Compliance No
Compliance Date 12/25/2002 IMMEDIATELY
Description No electrical equipment shall be installed, altered, renewed, replaced, or connected without first procuring a permit. ( From the ]
Item # 2
Description
time the hospital opened to over a year later Kris was on site ¢0~¢ucting extra time & material work without permits or
, , spect ons) To
Code Cooling Tower Pent. Compliance No. Compliance Date 12/25/2002 IMMEDIATELY
~eperation of power wiring & CL2 wiring.
Item # 3
Description
Code ELEVATOR AREA Compliance No ~.~ Compliance Date 12/25/2002 IMMEDIATELY
Code MECH. RM 02005 ___¢~mpl~ance No Compliance Date 1~25/2002 IMMEDIATELY J
Item # 4
Description
lLSupport
for non-metallic liquid tight, cover for a'n open switch box, CL2 Wiring support for speakers
Item # 5
Description
Code CONFERENCE RM "B" Compliance No .._ / Compliance Date 12~25/2002 IMMEDIATELY
Flexible cords shall not violate NEC 400.
Page 1 of 4
OSHKOSH
ON THE WATER
· ~;~;'iNsPECTION SERVICES DIVISION
DEP~'~'ENT OF COMMUNITY DEVELOPMENT
Room 205
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Issue [)ate 11125102 Compliance Date 12/25/02 IMMEDIATELY
Address 500 S OAKWOOD RD
Sent to
Inspected By
Compliance No
Kevin Benner 236-5046
Name Address City State Zip Code
~j Owner I MERCY MEDICAL CENTER OSH INC PO BOX 3370 OSHKOSH WI 54903 -3370
[] Contractor I SUPERIOR ELECTRIC COMPANY 1775 E SHADY LN NEENAH WI 54956 -0000
k-J Other j __ 0 _-0000
Inspector
Required for Occupancy J Occupancy Commercial Notice ~C) First O Final ~ 1
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 12/25/02
!,ntroduction
o n June 21,2000 a final inspection was conducted for Mercy Medica Center. The final inspection was not approved but the
spital was occupied. I reviewed the outstanding violations with Kris Lamers from Superior Electric. I understoood that he
r.h...a_ ,d ,s. everal outstanding issues to address for the owner which is normal for a project of'this size. 'He assured me th at
vlo~auons would be corrected. It is my understanding that the following violations have not been addressed..
Item # 6
Code CAFETERIA Compliance No Compliance Date 12/25/2002 MMEDIATELY
uffet t~bles shall have covers on the any open boxes, liqui,dtight support to kitchen equipment, where circuit breakers are
ed for a disconnecting means and is not within sight & 50 a breaker lock shall be installed, receptacles shall be installed as
nn~tu~tsr.e~eea~tcr~inndOu?t th, e term, inals (90 d~.ree p?wer re~c. eptaAles to_be inv?rted), secure fixtures to grid,CL2 wirin,g secured
Cede COMP. ROOM Compliance No ~ Compliance Date 12/25/2002 IMMEDIATELY
Descr; priori
Item # 7
Description
iLStrain .~.~ellef cord connectors required for unsecured boxes, open boxes require covers
//
Item # 8
Description
Code MAINTENANCE SHOP Compliance ~'
questioned the male cord connectors hanging from the ceiling as to their use
Compliance Date 12/25/2002
Item # 9
Code AUTOPSY RO(~M Compliance
Compliance Date 12/25/2002
Description
Ipen
wiring in the overhead light
Item # 10
Description
Code CAT SCAN
Ipen wirew~ above the ceiling
Compliance No V~'
Compliance Date 12/25/2002 IMMEDIATELY
Page 2 of 4
CITY (~F OSHKOSH
"' DEPArTmENT ~)F COMMUNITY DEVELOPi~ENT 215 C~URCH AVE
OSHKOSH Room 205 PO Box 1130
ON THE WATERCORRECTION NOTICE OSHKOS, 54903-1130
Issue Date 11/___25/02 Compliance Date 12/25/02 IMMEDIATELY Compliance No....9___
Address 500 S OAKWOOD RD Inspected By Kevin Benner 236-5046
Name Address City State Zip Code
Sent to L~J owner I MERCY MEDICAL CENTER OSH INC PO BOX 3370 OSHKOSH WI 54903 .3370
~ Contractor ~ SUPERIOR ELECTRIC COMPANY 1775 E SHADY LN NEENAH WI 54956 -0000
___j Other ] 0 -0000
~ Inspector j
~ Required for Occupancy I Occupancy Commercial Notice ~) First ~t Final -- O Other
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division bythe Compliance Date of 12/25/02
.Introduction .~n June 21,2000 a final inspection was conducted i~or Mercy Medical Center. The final inspection was not approved but th e
pospital was occupied. I reviewed the outstanding violations with Kris La~ers from ~S, uperior Electric. I understoood that he
!nad several outstanding issues to 'address for the owner which is normal ,or a projec, el= this size. 14e assured i-r~e that the
Iiolations would be corrected. It is my understanding that the'f011owing violations have not been addressed.
Item # 11
Description
Code RADIOLOGY Compliance Compliance Date 12/25/2002
~Tempo.r~ry lights were still installed above the ceiling, CL2 wiring shall not be secured to the cor~uit, s
Item # 12
Description
Code MRI Machine Compliance ~
Ieperation of CL2 wiring & power wiring from the disconnect to the unit.
Compliance Date 12/25/2002
Item # 13
Description
Code Med Office Area Complian~:e q/~"~/' Compliance Date 12/25/2002
upport for AC cable from light to light, CL 2 wiring r~ot supported from the building structure (laying on the gdd & ty-rapped to
MT,
Item # 14 Code Audio Room 1St Floor Compliance Compliance Date 12/25/2002
Description jFlexible cor;duit feeding Ceiling re,ceptacle(s) over 6' in length requires support within 12" of a fitting & every 4.5', conduit
[support for the transformer
Item #
15 Code NEC300-21 Compliance No ~. ~'/"~¢'" Compliance Date 12/~5/2002 IMMEDIATELY
Openingsaround electrical penetrations through fire resistant-rated walls partitions, floors, or ceil ngs, shall be firestopped
~,sing approve,d, methods to maintain the fire resistance rating.(I noti~.ced n the removed ceilings for the existing remodel that
~the rating of a ~.all has been violated & with the amount of T&M wor < that was conducted without inspection I assume this is
Iot the only violation of this code). .
Description
Page 3 of 4
¢ INSPECTION SERVICES DIVISION CITY OF ~SHKOSH
'~ DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CFIui~CH AVE
OSHKOSH Room 205 PO Box 1130
ON THE WATER CORRECTION NOTICE OSHKOSH WI 54903-1130
Issue Date 11/25/02 Compliance Date 12/25/02 IMMEDIATELy
Address 500 S OAKWOOD RD
Name Address
Sent to ~J Owner t MERCY MEDICAL CENTER OSH INC. PO BOX 3370
.... L~ Contractor ~ SUPERIOR ELECTRIC COMPANY 1775 E SHADY LN
[] Other I ..
[] Inspector ~
Inspected By
Compliance No.
Kevin Benner 236-5046
City State ZiP Code
OSHKOSH WI 54903 ,3370
NEENAH
WI .5495~6-000.~
0 -0000
LJ Required for Occupancy I Occupancy Commercial Notice ~ First · Final -~ Other ]
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, tl~e owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division' by the Compliance Date of 12/25/02
Introduction ~On June 21,2000 a final inspection was conducted for Mercy Medical Center. The final inspection was not approved but the
~ospital was occupied. I reviewed the outstanding vic at ons w th Kris Lamers from Superior Electric. I understoood that he
~n.ad several outstanding issues to address for the owner wh ch is normal for a project of this size. He assured me that the
I iolations would be correCted. It is my understanding that the following violations have not been addressed.
Item # 16
Description
Code Mechanical Room Compliance ~ Compliance Date 12/25/2002
.here is a termination box for a supplemental back-up generator. This installation has an opening in the bottom of the box for
~he entrance & termination of conductors. This open ng does not provide strain relief for the conductors and the terminals
jwould require that only a licensed electrician make that termination I discussed with Kris the use cfc cam-lock style cable
~c0nnectors which would cure bot.h violatioRs. Nothing has been done o[; addressed./pre~ous discussion.6/25/02, last 4 ~ ,,
Item # 17 Code NEC 51'7 Compliance No ~ Compliance Date 12/25/2002 IMMEDIATELY
Description ~Nith the addition of the chillers to the generator I required documentation & witness 10~d shedding of the chillers from the
generator. I have not been invited for the test nor has ICad Shedding information been provided.
_Summary lin a recent discussion with Kris, he mentioned that becauso ,he is no longer employed by Superior Electric & that I should of
iade him correct them 2 years ago. Any questions or concerns please feel free to contact me at 236-5046.
!.7_ .... D~i~fENCIE~. MUST BE CORRECTED AND APPROVED BEFORE clNoEALMENT, cALL (920)236-5050 F~OR
Signature
b~~' - ~ Date
ere violations list d on this report have been corrected in compliance with the applicable codes,
Print Name
Company
Signature Date ,