HomeMy WebLinkAbout2002-Letter (Bldg & HVAC Plan Review) r , CITY HALL Inspection Services Div 215ChurchAvenue City of Oshkosh PO Box 1130 OOshkosh WI � 54903-1130 OIHKOIH ON THF WATEF December 26`h, 2002 Tom Rhoner James Larson 17327 Via Del Campo 600 S Main St San Diego, CA 92127 Oshkosh, WI 54902 Re: Re-establishing Fire Walls 801 Oregon St 807 Oregon St 811 Oregon St File#G6-117-1202 The above-reference plans have been stamped CONDITIONALLY APPROVED based upon review for conformance to the current edition of the Wisconsin Administrative Building and Heating, Ventilating and Air Conditioning Code, chapters COMM 50-64, 66 & 69. These plans have NOT been reviewed for conformance to the Plumbing Code (chs. COMM 81-86), the Electrical Code (ch.COMM 16) and any COMM code not specifically mentioned. This approval is not a Building Permit. Necessary city permits must be secured before commencing work. You aze hereby advised that the owner, as defined in Chapter 101.01 (I) of the Wisconsin State Statutes, is responsible for all code requirements not specifically cited herein. Code requirements are set forth in Chapters 50 through 69 of the rules of the Department of Commerce. The building will be inspected during construction and a final inspection will be made after completion to insure compliance with city and state codes. The azchitect, professional engineer,builder or owner shall keep at the building as evidence of approval, one set of plans bearing the stamp of approval. COMM 51.15 All buildings shall meet exiting requirements on all floor levels. Second floor plans were not provided with this review. All building, electric,plumbing and HVAC shall be split so each building contains only its own mechanical facilities. For example, electrical within 811 Oregon cannot be run off of the adjoining building's electric service. COMM 51.02 Each firewall shall comply with the parapet wail requirements of this code section. , ' cirr Hn�� Inspection Services Div 215ChurchAvenue City of Oshkosh PO Box 1130 OOshkosh WI � 54903-1130 OIHKOIH oN rHF wnrEx COMM 51.044 All openings and penetrations through the rated building sepazation walls shall be fire rated per this code section. COMM 50.10 When all alterations are completed, the supervising professional shall file the required compliance statements. Sincerely, Director f Ins ction Services AD/lan