October 2 � 1991.
Mr . Kevin Uhen
Square "D" Company
3300 Medalist Dr .
Oshkosh � W1 54901
Re : Cross—connection inspection
llear Mr . Uhen
Reference our conversaY.ion durinq my inspection o₹ the installa—
tion by Lentner Ylumbinq of two °Iteduced Lone Backflow" protec—
tion devi.ces . ThP water suppLy piping on the outl.et side of the
two RP Valves must be labeled to indicate That non—potable water
is being distribuT.ed . The Administrative Code allows the use of
color coding or specific shaped tag application for the required
markinc� (Yellow for non—potable and Green for potable) . Any IIOSP.
outlets must also carry a label identifyinq them as "Sa£e" or
"Not Sate" outlets .
If you have any questions concerning this mater please feel free
to call . l7.36-50491
Sincerely�
Richard Wood
Plumbinq Supervisor
�
OlHKOJN City of Oshkosh
oN rHE wnrEa
October 2 � 1991
Dave Kind
2entner Plumbing & Heating
2860 Oreqon St .
Oshkosh� WI 54901
Re : Installation ot NY Valves for Sq�are "D" of Oshkosh
Dear Mr . Kind�
Inspection of the Heduced 'Zone Principle Backf7.ow YroY.ection
Valves installed at Square "D" of Oshkosh by your firm found the
followinq requires correction :
( 1 ) The emerc�ency wash station located on the south si..de of
the "Three Staqe Parts Washer" must be supplied with potable
water . (:urrently the staTion is supplied on the down stream
si-de of the RY Valve .
( 2 ) 'Phe water distribution on the downstream s� de of the RP
Valve must be indentified as reqiilred under the potabl.e
non-potable guidelines of ILHR 8'2 . 40 .
When correction is completed please notify my office Yor a rein—
spection .
If you have any quesT.ions concering this maY.er pl.ease feel free
to cal. l . ( 236-5049 )
Sinr.erely�
Richard Wood
Plumbinq Supervisor