HomeMy WebLinkAboutWater Filtration Clearwaters ReplacementI%
CITY OF OSHKOSH
VALVES PROCUREMENT PACKAGE FOR THE
WATER FILTRATION PLANT CLEARWELLS REPLACEMENT PROJECT
BID PROPOSAL FORM
In compliance with the advertising for Bids and having carefully examined the Drawings
and Specifications for the Work and the Site of the proposed Work and having determined
all of the conditions of the Work, the rules, regulations, laws, codes, ordinances, and other
governing circumstances relating to this Project, we, the undersigned, propose to furnish all
materials per the Project Specifications or noted deviations for the following amount(s):
Acknowledgement of addendum of
TOTAL BASE BID
o no. 4
$ I`72I�'
e�
Thc�usan.ci
-1+/lZ
(Base Bid Price in Words)
vtid vas 6 n l `/
Work to commence in I W `<S after receipt of order .Ln5•4-a 11 6/ ti76 s)
Terms: 3y daVS
Estimated delivery time after approved shop drawings (number of weeks):.2i4-3 U Lc.la4kS
SIGNATURES
Date: 1 "28 " 2� Name of Company: , n v,' ne t"' Co vh pt_it V
Submitted by: (name/title) Pt4<- Pa-,,10 W, Ch ie� Rltnail: �4C� dyr nrrc'��lUth
Address of Company: NG1 wL o 3 S, I wy, S i-i nei Or Phone:-2GZ--'?32-2a97
S uSSex M I S30 '9
Company Representative that will be named Project Manager for this Project, if awarded
the Bid:
Name: R_ FIP01��4 Title: C k I Q-� E sue} i Mcc- re
Company Representative authorized to sign contractsr electronically via DocuSign:
Name: Email: ►'S"tC�n�d �a�n�rGo, CvN1
To: City Of Oshkosh
Ref: Water Plant Clearwell Valve Replacements
Bid: January 31, 2025 @ 10:00 AM
Eng: Jacobs Engineering
Section: 40 27 02
Date:
1 /27/2025
Proposal No,
Q223dzos
Page:
one of one
Industry Code:
4952:
FOB: Factory Make Order To: Dorner Company
Terms: N30 N61 W23043 Silver Spring'Dr.
Delivery: 24-30 weeks estimated Sussex, WI 53089
Phone No: (414) 704-9010
Fax No: (262)-932-2101
By: Gordle Hoeft
Drnnernrt Ru• Ppfp Preneld
This quotation is valid only upon receipt of order for all quantities listed and are subject to the manufacturer's terms &
conditions and warranty (available upon request). Although we have attempted to make a complete take -off, we cannot
guarantee quantities. Delivery quotes represent an estimate only, and are quoted as "subject to prior sale". State & local
taxes are not Included, Tax exempt certificates must be provided, Final acceptance by Dorner Company, Sussex, WI
Item I
Quart. I
Description
Unit Price
Total
V-6101
V-6102
2
36" V500S DeZurik BAW Butterfly Valve. Cast iron body,
flanged ends, BUNA N packing/seat, class 1508, ductile Iron
disc with 316 edge, 304SS shaft, SS extension stem +
floorstand. CIL of valve to base of floorstand = 216". Auma
electric actuator. Model BAW, 36, F1, Cl, NBRN-NBR, 150B,
DI-S1, AIS, S41SD1*MGB-WR3L-N, Auma SA14.6.54B,
$ 86,350
$ 172,699
Electric actuator with features below:
Openlclose service
480/60/3 power
Six programmable relays
Side mounted handwheel override
Space heater in switch compartment
Aumatic non -intrusive controls including mechanical
reversing starteers, power supply, phase discriminor, local
control station, 20 X 4 character LED display
120 VAC control voltage
MWG position transmitter,
Double seal terminal compartment
NEMA 613 enclosure
60 second speed of operation
Total
$ 172,699
NOW une ji) startup service mcruaeu m price ur valve
Note: Exception to specification: 90 day completion after approval not possible.
BABA valveslactuators specified in bid have a delivery estiamted of at least 6
months.
NoteL Valves comply with Build America, Buy America (BABA) Act 2 CFR184 as derived from the
Environmental Protections Agency' Build America, Buy America Act Implementation procedures for
EPA office of Water Federal Financial Assistance programs (Nov, 2022)
Notes: Prices quoted are FOB Factory with freight allowed. Quote valid for 30 days,
Page 1
auma a
Solutions for a world in motion Product Configuration (0SHK0SH.1)
Configured by: Dorner Company
Configured on:1/27/2025
Printed:1/27/2025
DESCRIPTION SA14.6/AC01.2
INDUSTRY
Industry code Water, Wastewater
DEVICE CHARACTERISTICS
AUMA product Multi -turn electric actuator
Rated output torque [lbs.ft.] 370
Rated output torque [Nm] 502
Approximate weight (ibs.) 136
SERVICE CONDITIONS
Version
Weatherproof
Operating mode
OPEN - CLOSE duty
Enclosure protection
NEMA type 6P
Color
AUMA silver-grey (similar to RAL 7037)
Ambient temperature
-30 °C to +70 °C (-22 °F to +158 °F)
Nameplates
English - aluminum (US -AL)
Sealing elements
NBR - Nitrile Butadiene Rubber
Corrosion protection
KS
ELECTRICAL DATA
Mains voltage
480 Volts AC
Phase
3-Ph
Frequency
60 Hz
Type of duty
S2 -15 min.
Motor protection
(D-1T-0140) 3 thermal switches, 1 N.C. contact per phase wired in
series 140°C, class F insulation, tropicalized winding
Motor type
3 ph AC TENV motor, type AD/VD
MOTOR DATA
Caution
Ensure that the power conductors, and power source are sized
according to the max. current Imax [A].
Motor designation
AD00090-4-1.60
Nominal power (HP)
2
Nominal power (kW)
1.60
Nominal speed (RPM)
1,680
Nominal current In [A]
5.3
Max. current Imax [A]
9.0
Starting current la [A]
38.0
COS
0.57
ACTUATOR FEATURES
SA model
SA 14.6
Output speed
54 RPM
Valve attachment
FA14
Output drive
FA14-134 unbored
Torque switches
(0-M) torque sensing via MWG
Limit switches
(0-M) limit sensing via MWG
Position transm.
(30.5) MWG absolute encoder for AC 01.2
Turns per stroke
57.00
Operating time (seconds)
63
Stem protection tube
Without stem tube, with plastic protective screw plug, thread form
G21/2" BSPP
Heater
(22.5) 24 V in combination with controls: 5 W
Motor heater
(0) without
Torque switching
Setting range 150-370 Ibs.ft.
Set to close Ibs.ft.
370
Set to open Ibs.ft.
370
Handwheel
12.5" (315mm)
Close direction
RH - clockwise
Limit switching
(230) 1-500 rev/stroke adjustable with MWG
Lubricant
F15 Shell ALVANIA 1029
Special version TPA
(000) without
Electrical connection
(SO-000) actuator plug for mounting AM/SEM/AC
ACTUATOR CONTROLS
AUMATIC version
AC 01.2
Feedback E2
MWG magnetic limit/ torque sensor (non -intrusive setting)
Max. motor power
(800.02) Contactors for power class A2
Motor protection
(C00.01) thermal switch, automatic reset
Interface
(D00.01) Parallel 1/0 Interface
Positioner
(F00.00) Without
Input signals
(1100.01) CLOSE, OPEN, STOP, EMERGENCY •
Control voltage
(E00.02) 100 -120 V AC
Electronics supply
(A10.01) 24 V DC internal •
Output aux. voltage
(A30.02) 115 V AC - 30mA (internally powered) •
Output contacts
(1-100.03) 6 output contacts: 6 NO/NC without common 250V AC/SA •
Output signals
(500.01) default setting: K1=Fault, K2=End pos. CLOSED, K3=End pos.
OPEN, K4=Selector sw. REMOTE, KS=Torque fault CLOSE, K6=Torque
fault OPEN
Local controls
(1-00.01) selector switch LOCAL -OFF -REMOTE with padlock; push
buttons OPEN -STOP -CLOSE -RESET; large graphical LCD with a
resolution of 200 x 100 pixels
Activ. Bluetooth
(1.90.01) Switched on
Indication lights
(1-10.02) 1 CLOSED:green, 2 TRQ-CL:blue, 3 TH:yellow, 4 TRQ-
OP:violet, 5 OPEN:red, BLUETOOTH:blue (with numbers) •
Face plate
(US-ES-FR) English -Spanish -French •
Tolerance mains voltage
(A40.01) +/-10%
Electrical connection
(SB-080) plug/socket 100mm, 2 x %" NPT; 1 x 1 X" NPT •
Heater
(Q00.01) heater 24 V, internal supply •
Analog input 1
(P22.00) without
Analog input 2
(1330.00) without
Analog output 1
(1500.02) Position feedback: 4-20mA
Analog output 2
(1310.02) Torque feedback; 4-20mA
Blinker version
(N00.02) lights illuminated in mid travel (electronic)
Display language
English
Switch off in CLOSE
(042.01) Limit
Switch off in OPEN
(043.01) Limit
Self retaining LOCAL
(033.03) In direction OPEN and CLOSE
Self retaining REMOTE
(052.00) OFF
Safety mode
(153,01) OFF
Emergency function
(140.01) OFF
Torque by-pass
Function not active
Mounting position
Position A
Mounting pos, local controls
Position A-1, selector switch at 6 o'clock in relation to base of controls
(standard for SA/SQ)
Electrical connection mounting position
Position A
OPTIONAL EXTRAS
Double sealed at customer connection XK Yes
DRAWINGS
POINT-TO-POINT WIRING DWG
OUTPUT DRIVE/MOUNTING FLANGE DWG
ACTUATOR DIMENSIONAL DWG
OPERATION MANUALS
WIRING DIAGRAM LEGEND
DEVICE INTEGRATION MANUAL
ACTUATOR OPERATION MANUAL
SUPPLEMENT —ELECTRIC —INSTALL
TPCA-OA2-1 D1-AOOOTPAOOR100-011-000
SK099489
DDS000001 EAAKL341
Legend for AUMATIC AC 01.2/ACExC 01.2
Actuator controls AUMATIC AC 01.2/ACExC 01.2 Parallel
SAO 07.2 -16 2 with AC 01.2 Parallel Non -intrusive
Electrical installation guide