Wisconsin Department of Safety and Professional Services Phone: 608-266-2112
Division of Industry Services Web: http://dsps.wi.gov
4822 Madison Yards Way Email: dsps@wisconsin.gov
PO Box 7302
Madison, WI 53707 Tony Evers, Governor
Dan Hereth, Secretary
6/28/2024
CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 05/07/2025
CODE APPLIES: 05/21/2024
MUNICIPALITY:
CITY OF OSHKOSH
WINNEBAGO COUNTY
SITE:
UW OSHKOSH - SCOTT HALL
625 ALGOMA BOULEVARD
OSHKOSH, WI 54901
FOR:
625 ALGOMA BOULEVARD
Building Name: Scott Hall Restaurant- Fire Suppression
Object Type: Fire Suppression
Building Review Type: Alteration
Total Protected Area (Sq Ft): 2,998
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
SITE REQUIREMENTS
· Contact both the State Inspector and the local municipality PRIOR to the start of construction.
· A full size copy of the approved plans, specifications and this letter shall be on-site during construction and open to inspection
by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in
lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the
copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download,
print, and bind the full size set of plans along with our approval letter. A Department electronic stamp and signature shall be on
the plans which are used at the job site for construction.
The following conditions shall be met during construction or installation and prior to occupancy or use:
KEY ITEM(S):
· IBC 903.3.1.1 - Provide an automatic fire sprinkler system installation per NFPA 13.
· NFPA 13 (2013) 5.3.1.1 Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of other
occupancies where combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8
ft (2.4 m), and fires with moderate rates of heat release are expected.
Identification Numbers
Plan Review No.: CB-062400421-PRFS
Application No.: DIS-052423707
Site ID No.: 198189
Please refer to all identification numbers in each
correspondence with the Department.
DAVID DEWHURST
COMPLETE FIRE SOLUTIONS
2630 WEST AMERICAN DRIVE
NEENAH, WISCONSIN 54956
Storage 126, C-Store 127, and Kitchen / Prep 128 have been reviewed per this occupancy hazard classification. The
designer shall verify this occupancy classification is appropriate for these spaces.
· NFPA 13 (2013) 8.6.5.1.2 Sprinklers shall be arranged to comply with one of the following arrangements:
(1) Subsection 8.5.5.2, Table 8.6.5.1.2, and Figure 8.6.5.1.2(a) shall be followed.
The designer shall verify this section is met at the square ceiling feature at the entrance to Dining 127A and at the
drywall soffit shown at this room.
· NFPA 13 (2013) 9.2.1.3.3.1 Listed flexible sprinkler hose fittings and their anchoring components intended for use in
installations connecting the sprinkler system piping to sprinklers shall be installed in accordance with the requirements of
the listing, including any installation instructions.
Per the UL listing, the 48” Vicflex AH2 flexible drops are rated to 175 psi. The automatic fire sprinkler system will be
subjected to pressures beyond 175 psi at the altered area. However, the flex drops are also 200 psi rated when listed per
FM. Therefore, the flex drops shall be installed with a maximum of 3 – 7” radius bends per the FM listing criteria.
· NFPA 13 (2013) 23.4.4.1 For all systems the design area shall be the hydraulically most demanding based on the criteria
of Chapter 11, Chapter 12, or the special design approaches in accordance with the requirements of Chapter 22.
The designer shall conduct a proof calculation of Kitchen 128, Prep 128 and Storage 129. The designer may utilize
NFPA 13 sections 23.4.4.1.1.4 / 23.4.4.1.1.5. If more demanding, provide this updated hydraulic demand to the owner
and include it on the hydraulic placard at the system riser.
· SPS 361.31 - These plans were conditionally approved electronically. The designer is responsible to download the plans,
print out complete sets and permanently bind each set of the conditionally approved electronic plans, along with a complete
bound set of specifications, as submitted to the Dept., for reference in the field. Plans for field reference shall be the same size
and scale as originally submitted to the Dept. per SPS 361.31(2)(a), and per SPS 361.31(2)(d) shall be clear and legible. A
complete bound conditionally approved set of plans and set of specifications shall be made available to a Dept. representative
on-site upon request. There shall be an electronic stamp and signature on the index page of the conditionally approved plans
by the Dept. representative that conditionally approved the plans, as well as the professional of the project if the building is
over 50,000 cubic ft. Additionally, a copy of the conditional approval letter issued by the Dept. shall be permanently attached
to each of the conditionally approved plan sets.
· SPS 361.31(2)(e) - Provide additional calculations or information to substantiate that the submitted plans conform to code and
department policies.
In the future, plans submitted for review shall be provided with the following in eSLA:
· If a previous building plan review was conducted, it is imperative that the previous DIS# or CB# and accurate site
information is provided. Creating a site to circumvent providing this information is not acceptable.
Please provide this accurate information in the future to ensure that the plans will not be placed on hold until receiving
this additional information.
REMINDERS:
· SPS 361.33 - Where plan approval is required by this code, one set of plans, inclusive of a copy of all specifications, bearing
the stamp of conditional approval and a copy of the specifications shall be kept at the building site. The plans and
specifications shall be open to inspection by the department or its authorized representative.
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin
Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin
Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other
submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required.
All permits required by the state or the local municipality shall be obtained prior to commencement of
construction/installation/operation. You are responsible for complying with state and federal laws concerning construction near or on
wetlands, lakes, and streams.
This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protection water
supply, so contact the local fire department for further information.
In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should conditions arise
making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the
responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the design or
construction of the reviewed items.
Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file
compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be
filed online at https://esla.wi.gov/PortalCommunityLogin.
Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this
letterhead.
Sincerely,
Bob Jeske
Fire Protection Plan Reviewer
Division of Industry Services
Phone: (920) 492-5606
Email: bob.jeske@wisconsin.gov