HomeMy WebLinkAboutOshkosh Corrections DIS-042414540 Wisconsin Department of Safety and Professional Services Phone: 608-266-2112 Division of Industry Services Web: http://dsps.wi.gov 4822 Madison Yards Way Email: dsps@wisconsin.gov PO Box 7302 Madison, WI 53707 Tony Evers, Governor Dan Hereth, Secretary 5/13/2024 CONDITIONAL APPROVAL PLAN APPROVAL EXPIRES: 03/01/2026 CODE APPLIES: 04/02/2024 MUNICIPALITY: CITY OF OSHKOSH WINNEBAGO COUNTY SITE: OSHKOSH CORRECTIONAL INSTITUTION 1730 WEST SNELL ROAD OSHKOSH, WI 54901 FOR: 1730 WEST SNELL ROAD Building Name: Oshkosh Correction Institute - NSR-DU- Fire Suppression Object Type: Fire Suppression Building Review Type: New Total Protected Area (Sq Ft): 4,230 Fire Suppression Installation: Complete Occupancies: B - Business, Fire Sprinkler Type: Wet SITE REQUIREMENTS • Contact both the State Inspector and the local municipality PRIOR to the start of construction. • A full-size copy of the approved plans, specifications and this letter shall be on -site during construction and open to inspection by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download, print, and bind the full-size set of plans along with our approval letter. A Department electronic stamp and signature shall be on the plans which are used at the job site for construction. The following conditions shall be met during construction or installation and prior to occupancy or use: KEY ITEM(S): • IBC 903.3.1.1 - Provide an automatic fire sprinkler system installation per NFPA 13. • NFPA 13 (2013) 6.1.1.2 Unless the requirements of 6.1.1.3, 6.1.1.4, or 6.1.1.5 are met, all materials and devices essential to successful system operation shall be listed. Ensure all materials meet this standard. • NFPA 13 (2013) 6.2.9.1 A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. Ensure spare/replacements sprinklers and wrenches are present and available as required. Identification Numbers Plan Review No.: CB-052400301-PRFS Application No.: DIS-042414540 Site ID No.: 609499 Please refer to all identification numbers in each correspondence with the Department. PAUL BEHRINGER J. F. AHERN CO. 855 MORRIS STREET FOND DU LAC, WISCONSIN 54935 • NFPA 13 (2013) 6.7.4.1 All control, drain, and test connection valves shall be provided with permanently marked weatherproof metal or rigid plastic identification signs. Ensure adequate and accurate signage is present. • IBC 903.4 - All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all sprinkler systems shall be electrically supervised. Alarm, supervisory and trouble signals shall be automatically transmitted to an approved supervising station per NFPA 72. Actuation of the sprinkler shall activate the alarm. • SPS 361.31 - These plans were conditionally approved electronically. The designer is responsible to download the plans, print out complete sets and permanently bind each set of the conditionally approved electronic plans, along with a complete bound set of specifications, as submitted to the Dept., for reference in the field. Plans for field reference shall be the same size and scale as originally submitted to the Dept. per SPS 361.31(2)(a), and per SPS 361.31(2)(d) shall be clear and legible. A complete bound conditionally approved set of plans and set of specifications shall be made available to a Dept. representative on-site upon request. There shall be an electronic stamp and signature on the index page of the conditionally approved plans by the Dept. representative that conditionally approved the plans, as well as the professional of the project if the building is over 50,000 cubic ft. Additionally, a copy of the conditional approval letter issued by the Dept. shall be permanently attached to each of the conditionally approved plan sets. ALSO ADDRESS: • IBC 903.4.2 - Provide approved audible devices that are connected to every automatic sprinkler system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. • IBC 901.4 - Threads provided for fire department connections to sprinkler systems, standpipes, yard hydrants or any other fire hose connection shall be compatible with the connections used by the local fire department. Ensure FDC is acceptable to the fire department. • IBC 912.2 - With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatu s The fire department connection shall be installed in an accessible location acceptable to the fire chief. Ensure FDC location is acceptable to the fire department. REMINDERS: • SPS 361.33 - Where plan approval is required by this code, one set of plans, inclusive of a copy of all specifications, bearing the stamp of conditional approval and a copy of the specifications shall be kept at the building site. The plans and specifications shall be open to inspection by the department or its authorized representative. • Municipal Building Official, please forward a copy of this letter to the official in charge of conducting fire department inspections in your municipality. The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required. All permits required by the state, or the local municipality shall be obtained prior to commencement of construction/installation/operation. You are responsible for complying with state and federal laws concerning construction n ear or on wetlands, lakes, and streams. This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protectio n water supply, so contact the local fire department for further information. In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should condi tions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the desi gner of the responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the des ign or construction of the reviewed items. Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be filed online at https://esla.wi.gov/PortalCommunityLogin. Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this letterhead. Sincerely, Alex Payne Division of Industry Services Phone: 608-261-0354 Email: alex.payne@wisconsin.gov cc: BRIAN NOE, DIS INSPECTOR, 920-420-4796, BRIAN.NOE@WISCONSIN.GOV DIANE BARTLETT, MUNICIPAL CLERK, 920-236-5094, DBARTLETT@CI.OSHKOSH.WI.US GARY STUEWER, STATE OF WI DFD ZACHARY GIEMZA, J. F. AHERN CO. KAREN RABE, J. F. AHERN CO.