Wisconsin Department of Safety and Professional Services Phone: 608-266-2112
Division of Industry Services Web: http://dsps.wi.gov
4822 Madison Yards Way Email: dsps@wisconsin.gov
PO Box 7302
Madison, WI 53707 Tony Evers, Governor
Dan Hereth, Secretary
5/13/2024
CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 05/13/2025
CODE APPLIES: 04/09/2024
MUNICIPALITY:
CITY OF OSHKOSH
WINNEBAGO COUNTY
SITE:
RIVER VALLEY CHURCH
425 NORTH WASHBURN ST
OSHKOSH, WI 54904
FOR:
425 NORTH WASHBURN ST
Building Name: River Valley Church- Fire Alarm
Object Type: Fire Alarm
Building Review Type: Alteration / Change of Occupancy
Total Protected Area (Sq Ft): 24,120
Occupancies: A-3 - Other Assembly Uses, B - Business
Fire Alarm Installation: Complete
Fire Alarm System: Automatic Detection;Manual Alarm
Supervising Station: Central Station
SITE REQUIREMENTS
· Contact both the State Inspector and the local municipality PRIOR to the start of construction.
· A full size copy of the approved plans, specifications and this letter shall be on-site during construction and open to inspection
by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in
lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the
copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download,
print, and bind the full size set of plans along with our approval letter. A Department electronic stamp and signature shall be on
the plans which are used at the job site for construction.
The following conditions shall be met during construction or installation and prior to occupancy or use:
KEY ITEM(S):
· IBC 907.2.1 - A manual fire alarm system shall be installed in accordance with NFPA 72 in Group A occupancies having an
occupant load of 300 or more. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire
alarm system as required for the Group E occupancy.
The plans have been reviewed per this code section. As an emergency voice/alarm communication fire alarm system has
Identification Numbers
Plan Review No.: CB-052400240-PRFA
Application No.: DIS-042415553
Site ID No.: SIT-129188
Please refer to all identification numbers in each
correspondence with the Department.
JASON KARNZ
MARTIN SYSTEMS INC
2744 MANITOWOC RD
GREEN BAY, WISCONSIN 54311
not been provided, the occupant load at this building will not exceed 999 per IBC 907.2.1.1. Additionally, the classroom
areas have been reviewed per IBC 303.1.4 and a letter dated February 7, 2024 from River Valley Church Associate Pastor
Wyatt Fischer. The letter, in part, indicates the following: “Our educational spaces (including rooms 118-124) are intended
to serve children during Sunday worship services. Parents will drop off children in these rooms and remain on site, picking
children up after about one hour. We do not intend to offer “daycare” services”.
· IBC 907.6 - Provide a fire alarm system installed in accordance with NFPA 72.
· NFPA 72 (2013) 17.7.5.6.5.1 If doors are to be closed in response to smoke flowing in either direction, the requirements
of 17.7.5.6.5.1(A) through 17.7.5.6.5.1(D) shall apply.
The smoke detectors indicated at the door holds shall be installed per this section. If exceeding 60” from the top of the
door frames to the ceiling, an engineering evaluation or additional detectors are required.
· NFPA 72 (2013) 18.5.5.4.1 - Provide spacing that is in accordance with Tables 185.5.4.1 (a) or Table 18.5.5.4.1(b).
The plans have been reviewed based upon the following mounting heights for ceiling mounted strobes:
- 15 cd – 30cd strobes – Mounted a maximum 10’-0” above finish floor
- 75 cd strobes - Mounted a maximum 20’-0” above finish floor
- 95 cd strobes - Mounted a maximum 30’-0” above finish floor
If the strobes are mounted at heights above those listed, the prescriptive spacing provisions of this section cannot be
utilized. The designer shall verify the ceiling heights indicated above correspond to the proposed mounting heights of
the ceiling notification appliances.
· SPS 361.31 - These plans were conditionally approved electronically. The designer is responsible to download the plans,
print out complete sets and permanently bind each set of the conditionally approved electronic plans, along with a complete
bound set of specifications, as submitted to the Dept., for reference in the field. Plans for field reference shall be the same size
and scale as originally submitted to the Dept. per SPS 361.31(2)(a), and per SPS 361.31(2)(d) shall be clear and legible. A
complete bound conditionally approved set of plans and set of specifications shall be made available to a Dept. representative
on-site upon request. There shall be an electronic stamp and signature on the index page of the conditionally approved plans
by the Dept. representative that conditionally approved the plans, as well as the professional of the project if the building is
over 50,000 cubic ft. Additionally, a copy of the conditional approval letter issued by the Dept. shall be permanently attached
to each of the conditionally approved plan sets.
ALSO ADDRESS:
· IBC 907.4.2.2 - The height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 48 inches,
measured to the activating handle or level of the box.
REMINDERS:
· IBC 907.7 - Acceptance tests and completion - Upon completion of the installation, the fire alarm system and all fire alarm
components shall be tested in accordance with NFPA 72. A record of completion in accordance with NFPA 72 verifying that
the system has been installed and tested in accordance with the approved plans and specifications shall be kept for the life of
the system and be available to an authority having jurisdiction.
· SPS 361.33 - Where plan approval is required by this code, one set of plans, inclusive of a copy of all specifications, bearing
the stamp of conditional approval and a copy of the specifications shall be kept at the building site. The plans and
specifications shall be open to inspection by the department or its authorized representative.
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin
Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin
Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other
submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required.
All permits required by the state or the local municipality shall be obtained prior to commencement of
construction/installation/operation. You are responsible for complying with state and federal laws concerning construction near or on
wetlands, lakes, and streams.
This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protection water
supply, so contact the local fire department for further information.
In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should conditions arise
making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the
responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the design or
construction of the reviewed items.
Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file
compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be
filed online at https://esla.wi.gov/PortalCommunityLogin.
Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this
letterhead.
Sincerely,
Bob Jeske
Fire Protection Plan Reviewer
Division of Industry Services
Phone: (920) 492-5606
Email: bob.jeske@wisconsin.gov