CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 05/07/2025
CODE APPLIES: 03/25/2024
MUNICIPALITY:
CITY OF OSHKOSH
WINNEBAGO COUNTY
SITE:
UW OSHKOSH - SCOTT HALL
625 ALGOMA BLVD
OSHKOSH, WI 54901
FOR:
625 ALGOMA BLVD
Building Name: Kitchen Hood
Object Type: Kitchen Hood
ID No.: Kitchen Hood
SITE REQUIREMENTS
•Contact both the State Inspector and the local municipality PRIOR to the start of construction.
•A full size copy of the approved plans, specifications and this letter shall be on-site during construction and open to inspection
by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in
lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the
copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download,
print, and bind the full size set of plans along with our approval letter. A Department electronic stamp and signature shall be on
the plans which are used at the job site for construction.
Identification Numbers
Plan Review No.: CB-052400001-PRBK
Application No.: DIS-032413414
Site ID No.: 198189
Please refer to all identification numbers in each
correspondence with the Department.
AMY HASSELMAN
KONTEXT ARCHITECTS
242 E. MAIN ST, SUITE 201
SUN PRAIRIE, WISCONSIN 53590
Building Name: UW OSHKOSH - SOUTH SCOTT HALL
Object Type: Building
Major Occupancy: R-2 - Apartments, Dormitories, Monasteries, etc.
Class of Construction: IB - Fire Resistive Construction
Building Review Type: Alteration
Plan Type: Full/Complete Building
Total Floor Area in Sq Ft: 1,305
Sprinklered Type: NFPA 13
Structural Components Included in Review: None
Alteration Level: Two
The following conditions shall be met during construction or installation and prior to occupancy or use:
REMINDERS:
•SPS 361.36(1)(c) - This approval will expire 1 year after the date of this letter if the work covered by this approval is not
completed and the building ready for occupancy within that year. This conditional approval is only for the altered portions and
systems of the building shown on the plans. All other areas of the building have not been reviewed and are not a part of this
approval.
•IMC 506.3.6 - Kitchen hood exhaust ducts or canopy exhaust ducts serving a Type I hood shall be located at least 18 inches
from combustibles, or listed code exception shall be met. Use of a grease duct enclosure wraps are acceptable per Exception 3
assuming they meet ASTM E 2336 and are listed for such use. Also review IMC 308.6 for the acceptance of other listed
tested products or assemblies. For application of the IMC, gypsum board is considered a combustible material.
•IMC 507.2.6 - Type I kitchen exhaust hoods shall have a minimum clearance of 18 inches from combustibles, unless a
clearance reduction method of IMC 308.4.1 or 308.4.2 is used, or the hood is wrapped with a tested product per IMC 506.3.11
inclusive ASTM E2336; or IMC 308.4.1 with reduced or "zero" clearance to combustibles, or the code exception is met.
Instructions for such a tested product shall be on-site and available to a Dept. representative. All materials in a
noncombustible concealed space, used in conjunction with the exception listed in IMC 507.2.6, shall follow the rules defined
under IBC 718.5. For application of the IMC, gypsum board is considered a combustible material. The building and the
HVAC designers are reminded to coordinate efforts.
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin
Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin
Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other
submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required.
All permits required by the state or the local municipality shall be obtained prior to commencement of
construction/installation/operation. You are responsible for complying with state and federal laws concerning construction near or on
wetlands, lakes, and streams.
This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protection water
supply, so contact the local fire department for further information.
In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should conditions arise
making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the
responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the design or
construction of the reviewed items.
Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file
compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be
filed online at https://esla.wi.gov/PortalCommunityLogin.
Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this
letterhead.
Sincerely,
Jason Hansen
Building Plan Reviewer