HomeMy WebLinkAbout220 N Main St-Fire Suppression DIS-112348804 Wisconsin Department of Safety and Professional Services Phone: 608-266-2112 Division of Industry Services Web: http://dsps.wi.gov 4822 Madison Yards Way Email: dsps@wisconsin.gov PO Box 7302 Madison, WI 53707 Tony Evers, Governor Dan Hereth, Secretary 4/15/2024 CONDITIONAL APPROVAL PLAN APPROVAL EXPIRES: 12/13/2024 CODE APPLIES: 11/14/2023 MUNICIPALITY: CITY OF OSHKOSH WINNEBAGO COUNTY SITE: 220 NORTH MAIN STREET REMODEL 220 NORTH MAIN STREET OSHKOSH, WI 54901 FOR: 220 NORTH MAIN STREET Building Name: 220 North Main Street- Fire Suppression Object Type: Fire Suppression Building Review Type: REVISION Total Protected Area (Sq Ft): 22,185 Fire Suppression Installation: Complete Occupancies: M - Mercantile, R-2 - Apartments, Dormitories, Monasteries, etc. Fire Sprinkler Type: Wet SITE REQUIREMENTS · Contact both the State Inspector and the local municipality PRIOR to the start of construction. · A full size copy of the approved plans, specifications and this letter shall be on-site during construction and open to inspection by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download, print, and bind the full size set of plans along with our approval letter. A Department electronic stamp and signature shall be on the plans which are used at the job site for construction. · The following conditions shall be met during construction or installation and prior to occupancy or use: KEY ITEM(S): The plans have been revised to remove sprinkler protection from a portion of the crawl space. Additionally, the first floor room layout has changed in the southeast portion of the floor. Lastly, several conditions of approval from the original plans were addressed. The pipe sizes for the second floor have inadvertently been removed from the revised submitted plans. The pipe sizes for the Second Floor shall match the pipe sizes shown in the revised calculations and the original plans submitted for CB-122300931- PRFS and conditionally approved on December 13, 2023. Identification Numbers Plan Review No.: CB-122300931-PRFS Application No.: DIS-112348804 Site ID No.: SIT-124001 Please refer to all identification numbers in each correspondence with the Department. DALE BUSHMAKER USA FIRE PROTECTION 15775 W. SCHAEFER CT NEW BERLIN, WISCONSIN 53151 Plan Review Revision ID No.: SR-24-10814 Per the submitted plans, the basement and first floor levels are designed to NFPA 13 standards. The second floor apartments are designed to NFPA 13R standards. There is a two hour horizontal assembly between the first and second floors. · IBC 903.3.1.1 - Provide an automatic fire sprinkler system installation per NFPA 13. · NFPA 13 (2013) 8.6.3.4.1 Unless the requirements of 8.6.3.4.2, 8.6.3.4.3, or 8.6.3.4.4 are met, sprinklers shall be spaced not less than 6 ft (1.8 m) on center. The designer shall verify this section is met for minimum spacing at node S302 at the First Floor Mercantile plan. · IBC 903.3.1.2 - Provide an automatic fire sprinkler system installation per NFPA 13R. · NFPA 13R (2013) 7.4 Pipe Sizing. Piping shall be sized using hydraulic calculation procedures in accordance with NFPA 13. The designer shall verify the hydraulic calculations for remote areas #2. Where the sprinklers are attached to the 2” main (S200-200, S201-201, S202-202, and S203-203), the calculations indicate this small amount of piping to be 2” in size. If 1” in size, please revise the calculations. If more demanding, provide this hydraulic demand information to the owner and include it on the hydraulic placard at the system riser. · SPS 361.31 - These plans were conditionally approved electronically. The designer is responsible to download the plans, print out complete sets and permanently bind each set of the conditionally approved electronic plans, along with a complete bound set of specifications, as submitted to the Dept., for reference in the field. Plans for field reference shall be the same size and scale as originally submitted to the Dept. per SPS 361.31(2)(a), and per SPS 361.31(2)(d) shall be clear and legible. A complete bound conditionally approved set of plans and set of specifications shall be made available to a Dept. representative on-site upon request. There shall be an electronic stamp and signature on the index page of the conditionally approved plans by the Dept. representative that conditionally approved the plans, as well as the professional of the project if the building is over 50,000 cubic ft. Additionally, a copy of the conditional approval letter issued by the Dept. shall be permanently attached to each of the conditionally approved plan sets. ALSO ADDRESS: · IBC 901.6.1 - Automatic sprinkler systems shall be monitored by an approved supervising station. · IBC 903.4.2 - Provide approved audible devices that are connected to every automatic sprinkler system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. REMINDERS: · SPS 361.33 - Where plan approval is required by this code, one set of plans, inclusive of a copy of all specifications, bearing the stamp of conditional approval and a copy of the specifications shall be kept at the building site. The plans and specifications shall be open to inspection by the department or its authorized representative. The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required. All permits required by the state or the local municipality shall be obtained prior to commencement of construction/installation/operation. You are responsible for complying with state and federal laws concerning construction near or on wetlands, lakes, and streams. This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protection water supply, so contact the local fire department for further information. In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the design or construction of the reviewed items. Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be filed online at https://esla.wi.gov/PortalCommunityLogin. Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this letterhead. Sincerely, Bob Jeske Fire Protection Plan Reviewer Division of Industry Services Phone: (920) 492-5606 Email: bob.jeske@wisconsin.gov cc: BRIAN NOE, DIS INSPECTOR, 920-420-4796, BRIAN.NOE@WISCONSIN.GOV DIANE BARTLETT, MUNICIPAL CLERK, 9202365094, DBARTLETT@CI.OSHKOSH.WI.US THOMAS N RUSCH, RUSCH PROPERTIES JAMES BOHAN, USA FIRE PROTECTION