HomeMy WebLinkAboutNicolet Lumber Oshkosh Apt. DIS-122351855
Wisconsin Department of Safety and Professional Services Phone: 608-266-2112
Division of Industry Services Web: http://dsps.wi.gov
4822 Madison Yards Way Email: dsps@wisconsin.gov
PO Box 7302
Madison, WI 53707 Tony Evers, Governor
Dan Hereth, Secretary
1/12/2024
CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 01/12/2026
CODE APPLIES: 12/13/2023
MUNICIPALITY:
CITY OF OSHKOSH
WINNEBAGO COUNTY
SITE:
NICOLET LUMBER OSHKOSH APARTMENTS
OREGOON ST
OSHKOSH, WI 54902
FOR:
OREGOON ST
Building Name: RIPPLE ESTATES BLDG 6- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 1- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 2- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 3- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Identification Numbers
Plan Review No.: CB-012400028-PRFS
Application No.: DIS-122351855
Site ID No.: SIT-124913
Please refer to all identification numbers in each
correspondence with the Department.
JAKE BEHRINGER
BADGERLAND FIRE PROTECTION
5668 EXECUTIVE CIRCLE
LITTLE SAUMICO, WISCONSIN 54141
Building Name: RIPPLE ESTATES BLDG 4- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 5- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 7- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
Building Name: RIPPLE ESTATES BLDG 8- Fire Suppression
Object Type: Fire Suppression
Building Review Type: New
Total Protected Area (Sq Ft): 19,440
Fire Suppression Installation: Complete
Occupancies: R-2 - Apartments, Dormitories, Monasteries, etc., None
Fire Sprinkler Type: Wet
SITE REQUIREMENTS
Contact both the State Inspector and the local municipality PRIOR to the start of construction.
A full size copy of the approved plans, specifications and this letter shall be on-site during construction and open to inspection
by authorized representatives of the Department, which may include local inspectors. If plan index sheets were submitted in
lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that correspond with the
copy on file with the Department. If these plans were submitted in an electronic form, the designer is responsible to download,
print, and bind the full size set of plans along with our approval letter. A Department electronic stamp and signature shall be on
the plans which are used at the job site for construction.
The following conditions shall be met during construction or installation and prior to occupancy or use:
KEY ITEM(S):
IBC 903.3.1.2 - Provide an automatic fire sprinkler system installation per NFPA 13R.
NFPA 13R (2013) - 5.2.3.2 When nonmetallic pipe is used in combination systems utilizing steel piping internally
coated with corrosion inhibitors and nonmetallic piping, the steel pipe coating shall be investigated for compatibility
with the nonmetallic piping by a testing laboratory.
NFPA 13R (2013) - 5.2.3.4 When nonmetallic pipe is used in combination systems utilizing steel pipe, cutting oils and
lubricants used for fabrication of the steel piping shall be compatible with the nonmetallic pipe materials.
NFPA 13R (2013) - 5.2.3.5 Fire-stopping materials intended for use on nonmetallic- piping penetrations shall be
investigated for compatibility with the nonmetallic pipe materials.
NFPA 13R (2013) - 5.2.12.2.1.1 When nonmetallic fittings are used in combination systems utilizing internally coated
steel piping and nonmetallic fittings, the steel pipe shall be investigated for compatibility with the nonmetallic fittings
by a testing laboratory. Cutting oils and lubricants used for fabrication of the steel piping shall be compatible with the
nonmetallic fitting materials.
NFPA 13R (2013) - 5.2.12.2.1.3 Fire-stopping materials intended for use on nonmetallic fitting penetrations shall be
investigated for compatibility with the nonmetallic fitting materials.
NFPA 13R (2013) 6.4.1 Residential Sprinklers That Have Been Listed with Specific Coverage Criteria. Sprinklers
shall be installed in accordance with the coverage criteria specified by the listing.
Ensure sprinklers do not exceed manufacturer's specifications.
NFPA 13R (2013) 6.4.6.3.4.1 Pendent sprinklers shall be located at least 3 ft (914 mm) from obstructions such as
ceiling fans and light fixtures unless the requirements of 6.4.6.3.6 are met.
Ensure appropriate installation.
NFPA 13R (2013) - 6.4.6.3.5.1 Sidewall sprinklers shall be located at least 5 ft (1.52 m) from obstructions such as
ceiling fans and light fixtures unless the requirements of 6.4.6.3.7 are met.
Ensure appropriate installation.
IBC 901.6.1 - Automatic sprinkler systems shall be monitored by an approved supervising station.
IBC 912.2 - The fire department connection shall be installed in an accessible location acceptable to the fire chief.
REMINDERS:
SPS 361.31(2)(b) - A copy of this approval letter and index sheet shall be attached to plans that correspond with the copy on
file with the Department. Changes to the approved plan must be submitted for review and approval. Failure to properly attach
the approval and index page to the plans that match the copy on file with Department may result in enforcement action under
ss. 101.02 or 443.13, Statutes.
SPS 361.33 - Where plan approval is required by this code, one set of plans, inclusive of a copy of all specifications, bearing
the stamp of conditional approval and a copy of the specifications shall be kept at the building site. The plans and
specifications shall be open to inspection by the department or its authorized representative.
Municipal Building Official, please forward a copy of this letter to the official in charge of conducting fire department
inspections in your municipality.
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin
Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in chapter 101.01(10), Wisconsin
Statutes, is responsible for compliance with all code requirements. Only those object types listed above have been approved; other
submittals such as plumbing and those listed above under REQUIRED SUBMITTAL(S), may also be required.
All permits required by the state or the local municipality shall be obtained prior to commencement of
construction/installation/operation. You are responsible for complying with state and federal laws concerning construction near or on
wetlands, lakes, and streams.
This plan has not been reviewed for compliance with fire code requirements, including those for fire lanes and fire protection water
supply, so contact the local fire department for further information.
In granting this approval, the Division of Industry Services reserves the right to require changes or additions, should conditions arise
making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the
responsibility for designing a safe building, structure, or component. The Division does not take responsibility for the design or
construction of the reviewed items.
Per s. SPS 361.40(4), projects for buildings of over 50,000 cubic feet total volume shall have supervising professionals who file
compliance statements with this agency and the local code officials prior to occupancy of the project. Compliance statements shall be
filed online at https://esla.wi.gov/PortalCommunityLogin.
Inquiries concerning this correspondence may be made to me at the contact information listed below, or at the address on this
letterhead.
Sincerely,
Joseph Nowicki
Fire Protection Plan Reviewer
Division of Industry Services
Phone: 414-615-9848
Email: joseph.nowicki@wisconsin.gov
cc:
BRIAN NOE, DIS INSPECTOR, 920-420-4796, BRIAN.NOE@WISCONSIN.GOV
DIANE BARTLETT, MUNICIPAL CLERK, 9202365094, DBARTLETT@CI.OSHKOSH.WI.US
DENNIS HERMANS, NICOLET LUMBER CO