HomeMy WebLinkAboutBuilidng (stacked mezzanine-no smoke detection system) 12/1/2000 , -�
OINSPECTION SERVICES DIVISION
` �EPARTMENTOFCOMMUNITYDEVELOPMENT
OSHKOSH CITV OF OSHKOSH,WISCONSIN
ONTHEWATER CORRECTION NOTICE
IssueDate O9/052000 ComplianceDate 10/05/2000 IMMEDIATELV Compllanw No .
Address 2155 S OAKWOOD RD Inspectetl ey Allyn�annhoH _ _
Name Atldress �/ y � City State ZlpCotle
Sen��o � 0'++ner��, _� MERIDIANMKLLC . �S.> S. (J�i.p�oR' �t� �T�^ _ li� S`�r/OL
� Conlracror CRMEVER 895W20THAVE OSHKOSH WI 54902 - .
Other _ _
Inspecror �
� RequiretlforOccupancy Occupancy Warehouse Notice First Final Other 12-01-2000
invoduamn n insepction of the Stacked Meaanine revealed the smoke tletection system has not been inslalled per the
ariance conditions of approval.You have been allowed to occupy without Final Approval since May.2000. This
ust be completed immediately.
I[em p 1 Cotle Comm 50 Compliance No Compliance Date 70/OS/2000 IMMEOIATELV
Deseriptlon condition of variance to section 54.02(4) required a smoke detection sys[em to cover all areas wilhin 100'of the
erimeter of the stacketl mezzanine. This system is to provide complete coverage within the area measured 100'
round thepermiter of lhe mezzanine at the warehouse ceiling level. This has been confrmed with ihe reviewer.
su� p�ease advise me of your schedule to comply and arrange for a reinspection when complete. (236-5045). This is
he second notice since 9-5-00. Failure[o comply by 12-29-00 will resWt in citation issuance.
�
DEFICIENCIES MUST CORq2 TED ID APPROVED BEFO CONCEALMENT. CALL(920)2365050 FOR INSPECTION.
\
Signature Date /
Page t of 1